Stop the unit.
Is the high pressure 
protector broken? 
Check if the outdoor unit
ventilation is good.
Ensure that the outdoor unit’s
ventiliation is functioning properly.
High pressure protection
Connect the high pressure switch
and main control board.
Method: Disconnect the plug.
Measure the high pressure protector 
resistance. If the protector is normal,
the value is 0.
Does the problem still exist?
No
Replace the 
high pressure protector.
Yes
No
Refer to the “Fan Speed is operating 
outside of Normal Range” malfunction.
Is the outdoor fan running properly?
Is the heat exchanger dirty? Clean the heat exchanger.
Replace the outdoor main board.
Is the problem resolved?
Check whether the refrigerant
system is functioning properly.