DIAGNOSIS AND SOLUTION (CONT)
Indoor Units Mode Conflict (match with multi outdoor unit)
Description: The indoor units cannot operate in the COOLING mode and HEATING mode simultaneously. The HEATING mode is the
priority.
Examples:
If indoor unit A is operating in the COOLING mode or the FAN mode, and indoor unit B is set to the HEATING mode, unit A will power
off and unit B will continue to operate in the HEATING mode.
If indoor unit A is operating in the HEATING mode and indoor unit B is set to the COOLING mode or fan mode, unit B will change to
STANDBY mode and unit A will not change modes.
NOTE:
No: No mode conflict
Ye s: Mode conflict
COOLING MODE HEATING MODE FAN OFF
COOLING MODE No Yes No No
HEATING MODE Yes No Yes No
FAN No Yes No No
OFF No No No No