REFRIGERANT LINES
General refrigerant line sizing:
1 The outdoor uni ts are shipped with a full c harge of R410A
refrigerant. All charges, line sizing, and capacities are based on
runs of 25 ft (7. 6 m) per numbe r of zones . For runs over 25 ft
(7.6 m), consult long--line se ction on this page for prope r
charge adjustments.
2 Minimum refrigerant line length between the indoor and
outdoor units is 10 ft. (3 m).
3 Re frige r ant lines should not be buried in the gr ound. If it is
nece ssary to bury the li nes, not more tha n 36--in (914 mm)
should be buri ed. Provide a mi ni m um 6--in (152 mm) vertical
rise to the se rvice valves to prevent refrige r ant migration.
4 Both lines must be insulated. Use a minimum of 1/2--in.
(12.7 mm) thick insulation. Closed--cell insulation is
recommended in all long --line applications.
5 Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate
the tubing so that vibration or noise is not transmitted into
the structure.
IMPORTANT : Both refrigerant lines must be insulated separately.
S The following maximum lengths are allowed:
Table 16—Refrigerant Lines
System size 18K 27K 36K 48K
Piping
Min. Piping Length ft (m) 10 (3) 10 (3) 10 (3) 10 (3)
Standard Piping Length ft (m) 25 (7.5) 25 (7.5) 25 (7.5) 25 (7.5)
Max. outdoor--indoor height difference
ft (m) 32(10) 32(10) 32(10) 32(10)
(OU higher than IU)
Max. outdoor--indoor height difference
ft (m) 49(15) 49(15) 49(15) 49(15)
(IU higher than OU)
Max. Piping Length with no additional refrigerant
charge per zone.
ft (m) 24.6(7.5) 24.6(7.5) 24.6(7.5) 24.6(7.5)
Max. Length for one indoor unit ft (m) 65.6(20) 82(25) 98(30) 98(30)
Max. height different between indoor units ft (m) 32(10) 32(10) 32(10) 32(10)
Total Maximum Piping Length Ft. (m) 98(2*15=30) 147(3*15=45) 196(4*15=60) 245(5*15=75)
Additional refrigerant charge
Oz/ft (g/m) 0.16(15) 0.16(15) 0.16(15) 0.16(15)
(between Standard – Max piping length)
Gas Pipe in 3/8*2 3/8*3 1/2+3/8*3 1/2+3/8*3
Liquid Pipe in 1/4*2 1/4*3 1/4*4 1/4*5
Refrigerant
Refrigerant Type R410A R410A R410A R410A
Heat Pump Models Charge Amount Lbs (kg) 4.19 (1.9) 6.17 (2.8) 7.94 (3.6) 10.14 (4.6)
NOTE: The refrigerant charge included is adequate for the number
of zones multiplied by the max. piping length with no additional
refrigerant.
Long Line Applications,:
1 No change in line sizing is required.
2 Add refrigerant per Table 17.
Table 17—Additional Charge Table Per Zone
Unit
Size
To t a l L i n e Le n g t h
ftper indoor unit
Additional Charge, oz/ft.
ft (m)
Min Max
10 -- 25
(3 -- 8)
>25 -- 66
(8 -- 20)
>66 -- 82
(20 -- 25)
>82 -- 98
(25 -- 30)
18
10
66
None 0.16
27 82
0.1636
98 0.16
48