EasyManua.ls Logo

Carrier 40MBAB Series - EH0 E - Water-Level Alarm Malfunction

Carrier 40MBAB Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40MBAB: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
DIAGNOSIS AND SOLUTION (CONT.)
EH0E - Water-Level Alarm Malfunction Diagnosis and Solution
Description: If the sampling voltage is not 5V, the LED displays the failure code.
Recommended parts to prepare:
Connection wires
Water-level switch
Water pump
Indoor PCB
Troubleshooting and Repair:
Power off, then rest art the unit 2 minutes
later.
Is the water-level switch
inserted properly?
Insert the w ater-l evel sw it ch
properly
NO
YES
Replace the water-level switch
NO
YES
Replace the indoor main PCB
Does a problem
remain?
YES
The unit is operating normally.
NO
Is the water level
switch broken?

Related product manuals