AC power input voltage protection
Check whether
the power voltage is
normal.
Restart the unit when the power
supply is normal.
NO
Measure the outdoor terminal voltage.
YES
Is it normal?
Is the wiring of the power
wires well connected?
NO
Reconnect the wire well.
Measure the voltage
between L and N.
YES
Is it normal?
Is the L and N wiring
well connected?
NO
Measure the input voltage of
bridge rectier.
YES
Is it normal? NO
Measure the voltage between P and N
is normal, refer to Appendix 3.
YES
Is it normal? NO Replace the bridge rectier.
Check
whether the
bridge rectier
is normal.
Replace the PFC module (if available)
<(6
Check the
wiring of the reactor
or the inductance.
12
Reconnect the wiring.
Check whether
the reactor or inductance
is normal.
<(6
Replace the reactor
or inductance.
12
Replace the IPM board. If the IPM
board and main board is in a board,
replace the outdoor main PCB.
<(6
<(6
Reconnect the wire well.
Is the bridge rectier wiring
well connected?
Reconnect the wire well.