61
P4(Temperature protection of compressor discharge) error diagnosis and
solution.
Error Code P4
Malfunction decision conditions
When the compressor discharge temperature(T5) is more than 239_F for 10 seconds, the
compressor stops and restarts when T5 is less than 194
_F.
Supposed causes
S Refrigerant leakage
S Wiring mistake
S The discharge temperature sensor faulty
S Outdoor PCB faulty
Troubleshooting
ompressor disc
arge
compressor discharge
C
ec
w
et
er t
e
compressor disc
arge tem
s
ore t
an
15
C
Check whether the
compressor discharge temp. is
more than 239°F ?
heck whether the
connect
on
r
t
etween
compressor
sc
arg
tem
n
B
ccor
ng
to w
r
ng
agram
Check whether the
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
asure t
e res
stance va
ue
compressor discharge
tem
ensor
f the value is
ot norma
s
orma
re
er to
e Appen
ix
Measure the resistance value
of compressor discharge
temp. sensor. If the value is
not normal is normal refer to
the Appendix 2?
No
Yes
Yes
No
Correct the wiring connection
Stop leaking and add re
rigeran
Stop leaking and add refrigerant
ep
ace t
e compressor
sc
arge temp
ensor
Replace the compressor discharge temp. sensor
No
Yes
ep
ace
g
pressure va
ve ass
Replace high pressure valve assy
Yes
No
p
ace out
oor ma
nP
B
Replace outdoor main PCB
No
Check whether the
refrigerant is leak