SG-38MHRC-01                                                                            Specifications subject to change without notice.                                 45
Yes
Tighten the screws and apply 
silicon grease.
Replace the outdoor control PCB.
No
Ensure the fastening screws
on the PCB and IPM radiator 
are tight. 
For other models, 
Are the indoor and outdoor
units air ow systems
obstructed.
Clear the  air inlet and outlet or  the indoor 
and the outdoor unit’s heat exchangers.
Turn o the power supply. 
Wait ten minutes then turn back on.
Is the compressor top 
temperaure is higer than 90°C?
Are the connections, especially
the OLP connection (Over Load
Protector) sensor good?
Correct the connections.
Is the refrigerant system normal?
Measure the resistance
between the OLP’s two ports.
Is it zero?  
Replace the OLP.  
Repair the 
refrigerant system.