Legend and Notes for Tables 9-10
LEGEND
NOTES:
1. Minimum circuit amps (MCA) and maximum overcurrent protection
(MOCP) values are calculated in accordance with The NEC. Article
440.
2. Motor FLA values are established in accordance with Underwrit-
ers’ Laboratories (UL). Standard 1995.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the formula in the example (see column to
the right) to determine the percentage of voltage imbalance.
4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the 40RF
indoor fan motor per NEC Article 430-28 (1) or (2) (depends on
length of conduit between heater enclosure and 40RF power entry
location). Install wires in field-installed conduit.
Example: Supply voltage is 230-3-60
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
Table 9 — Electrical Data, Standard Motors — Two Speed
a
UNIT
NOMINAL
V-PH-Hz*
IFM
TYPE
UNIT VOLTAGE
RANGE
FAN MOTOR POWER SUPPLY
Min. Max. Hp kW FLA
Minimum
Circuit Amps
(MCA)
Maximum
Overcurrent
Protection
(MOCP)
40RFA*07
40RFQ*07
208/230-3-60
MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60
MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60
MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
40RFA*08
40RFS*08
40RFQ*08
208/230-3-60
MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60
MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60
MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
40RFS*10
208/230-3-60
MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60
MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60
MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
40RFA*12
40RFS*12
40RFQ*12
208/230-3-60
MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60
MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60
MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
NOTE(S):
a. See “Legend and Notes for Tables 9-10” on page 14.
Table 10 — Fan Contactor Coil Data
a
UNIT 40RF*
VOLTAGE
(vac)
MAXIMUM
HOLDING VA
07, 08, 12 24 10
NOTE(S):
a. See “Legend and Notes for Tables 9-10” on page 14
FLA Full Load Amps
HACR Heating, Air Conditioning, and Refrigeration
% Voltage
Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
=227
33
% Voltage Imbalance = 100x
4
=1.78%
227
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
A
B
C
MOTOR