Table 3 -- Electric Heater Data for Units with ECM (cont)
UNIT
40UV,UH100
(at1000 Cfm)
HP
'/3
NOMINAL
V/Ph/Hz
FLA
NUMBER
OF
ELEMENTS
3
4
5
6
3
4
5
6
3
4
5
0
3
4
5
6
3
4
5
6
3
4
5
6
MCA MOCP
31,5 39,4 40
41,1 51,4 66
208/1/60
50,8 63.4 70
50,4 75,5 80
35.9 44.9 45
47.1 58.8 60
240/1/80
58.2 72.7 80
69.3 88,5 90
31.2 39,0 40
40.8 51 .O 60
277/1/60
50.4 63.1 70
60.1 75.1 80
19.3 24.1 25
28.9 36.2 40
200/3/60
36.0 45.0 50
36.0 45.0 50
21.9 27.3 30
33.6 41.2 45
240/3/50
41.1 51.4 60
41.1 51.4 60
10.6 13,3 15
16.2 20.2 25
460/3/80
20.3 25.3 30
20.3 25.3 30
LAT
(F)
89
95
102
108
96
104
112
121
96
104
112
121
89
95
192
108
96
104
112
121
95
104
112
121
LEGEND
-- Direct Expansion
-- Full Load Amps
-- Leaving-Air Temperature at 70 F Entering-Air
TOTAL
CAPACITY
(kW)
6.0
8.0
10.0
11.9
8.0
10.7
13.3
16,0
8.0
10.7
13.3
16.0
6.0
8.6
10.0
11.9
8.0
10.7
13.3
16.0
8.0
10.7
13.3
16.0
DX
FLA
LAT
Temperature
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominalcfm.
2. Water and DX coils used on electric heat units have left-hand
coil connections.
3. Electric heat is availeble in the reheat positiononly and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
]6