20 42GW
... any obstruction of the unit air intake or supply grilles (See g. 3).
... exposure to oil vapours (See g. 4).
... installation in areas with high frequency waves (See g. 5).
... ascending sections of condensate drain piping.
These may only be used near the unit with a maximum height
difference of 200 mm from the top of the unit (See g. 6).
... horizontal sections or curves of condensate drain piping with less
than 2% slope (See g. 7).
... exposure to direct sunshine, when the unit is operating in the
cooling mode; always use shutters or shades.
... positions too close to heating sources which may damage the unit
(See g. 8).
... connecting condensate piping to sewage system drain without
appropriate trap.
Trap height must be calculated according to the unit discharge
head in order to allow sufcient and continuous water evacuation
(See g. 9-10).
... only partial insulation of the piping.
Non-level installation which will cause condensate dripping (See
g. 11).
... attening pipes or condensate pipes (See g. 12-13).
... slack on electrical connections (See g. 14).
For your safety, wear protective gloves!
Warnings: Avoid