42HQE009/012/018/022-38YE009/012/018/022  
GB - 8
Refrigerant piping connection
Flaring
• Cut a pipe with a pipe cutter.
• Insert a flare nut into a pipe and flare the pipe.
Outer diam. A (mm)
(mm) Max. Min.
Ø 6.35 1.3 0.7
Ø 9.53 1.6 1.0
Ø 12.7 1.8 1.0
Ø 15.88 2.4 2.2
Tightening Connection
• Align pipes to be connected.
• Sufficiently tighten  the flare  nut with fingers, and then tighten it
with a spanner and torque wrench as shown.
CAUTION
• Excessive  torque can  break nut depending on installation
conditions.
Outer diam. Tightening torque
Additional tightening
(N.cm) torque (N.cm)
Ø 6.35
1570 1960
(160kgf.cm) (200kgf.cm)
Ø 9.53
2940 3430
(300kgf.cm) (350kgf.cm)
Ø 12.7
2940 4410
(300kgf.cm) (450kgf.cm)
Ø 15.88
7360 7850
(750kgf.cm) (800kgf.cm)
Outdoor unit installation
90°C               
 Oblique   Roughness  Burr
A
Wiring connection
1. Remove the  electric parts cover  from the outdoor unit.
2. Connect the connective  cables to the terminals as identified
with their  respective matched  numbers on the terminal block of
indoor and outdoor units.
3. To prevent the ingress of  water, from a loop of the connective
cable as  illustrated in  the  installation diagram of indoor and
outdoor units.
4. Insulate unused cords (conductors) with PVC-tape. Process
them  so they do not  touch any electrical or metal parts.
CAUTION:
Wrong wiring connections may cause some electrical parts to
malfunction. A  disconnection device having an air gap contact
separation in all active conductors should be  incorporated in the
fixed wiring according to the National Wiring Regulation. All wiring
must comply with local and national electrical codes and be
installed by qualified and skilled electrician.
 Cover
 Screw
Terminal block of outdoor unit
38YE009/012/018
Terminal block of outdoor unit
38YE022
 Wire-holding Board
 Connective cable
(1, 2, 3, 4, 5)
CDU signal wire
(7, 8)
10 cm
40 cm
Connective cable
(Cooling & heating type)