(3) Dry Mode
This operation eliminates moisture effectively by operating the compressor, indoor and
outdoor fan motor intermittently, so that the room temperature is maintained at set
temperature.
Determination of dry mode BLOCK based on Room temp. and Set temp.
(Set temp. : Ts)
1) Initial determination of dry mode BLOCK
CBA
Ts2 Ts+1
2) Redetermination of dry mode BLOCK
C
B
A
Ts2Ts1 Ts+1 Ts+2
Operating state according to the each BLOCK
1) BLOCK A
COMP & ODF : ON
IDF : operate at LOW speed
2) BLOCK B
COMP & ODF : repeat ON for 5 min. and OFF for 5 min.
IDF : operate at ULO speed
3) BLOCK C
COMP & ODF : OFF
IDF : operate at ULO speed
NOTE :
1. Unit determines again the dry mode BLOCK by sensing Room temp.
every 5 min.
2. 3 min. minimum operation of compressor is not applied.