18
(3) Dry Mode
– This operation eliminates moisture effectively by operating the compressor, indoor and
outdoor fan motor intermittently, so that the room temperature is maintained at set
temperature.
– Determination of dry mode BLOCK based on Room temp. and Set temp.
(Set temp. : Ts)
1) Initial determination of dry mode BLOCK
CBA
Ts–2 Ts+1
2) Redetermination of dry mode BLOCK
C
B
A
Ts–2Ts–1 Ts+1 Ts+2
– Operating state according to the each BLOCK
1) BLOCK A
COMP & ODF : “ON”
IDF : operate at LOW speed
2) BLOCK B
COMP & ODF : repeat “ON” for 5 min. and “OFF” for 5 min.
IDF : operate at ULO speed
3) BLOCK C
COMP & ODF : “OFF”
IDF : operate at ULO speed
NOTE :
1. Unit determines again the dry mode BLOCK by sensing Room temp.
every 5 min.
2. 3 min. minimum operation of compressor is not applied.