19
(4) Automatic Operation
(42HQG007/009/012/018/024 & HWG195H/225H/305H/455H/605H)
If the unit is set to AUTO mode, the unit operates automatically by selecting COOL
or HEAT mode according to the room temperature to keep the room temperature
comfortable.
ROOM TEMPERATURE
T.S+1° C
T.S
T.S-1° C
COOLING MODE
HOLD CURRENT MODE
HEATING MODE
When the room temperature is lower than 21°C or is higher than 29°C, the unit
operates Heating or Cooling operation regardless of the user set temperature.
This Automatic operation is not suitable for the application to the computer
room or some food/wine stock storage
21° C
COOL/HEAT TRANSITION
HEATING
ONLY
COOLING
ONLY
SENSED
ROOM TEMP.
29° C