71
CORRECTION FACTOR OF COOLING AND HEATING
SYSTEM PERFORMANCES DUE TO
INDOOR / OUTDOOR PIPING LENGTH
UNIT PIPING LENGTH
SIZE 3 6 10 15 25
07 1.02 1 0.97 0.93 ==
09 1.02 1 0.97 0.93 ==
12 1.02 1 0.97 0.93 ==
18 1.01 1 0.99 0.97 0.95
24 1.01 1 0.97 0.95 0.93
EXTENDING RATINGS
13