71
System Heating Performance Data (Cont.)
Ducted Split System
53QDMT24-718 Heat Pump
220-240V/1Ph/50Hz
Indoor Conditions Outdoor Ambient Temperature
ESP
in.wg
Fan
Speed
Air
Flow
cfm
Temp. °C
DB
24/18°C DB/WB 7/6°C DB/WB 2/1°C DB/WB
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
0.20
in.wg
High
580
15°C
26665 2245 21455 1930 17590 1670
20°C 25755 2450 20430 2070 16565 1825
27°C 24125 2595 19200 2235 15545 1975
Medium 500
15°C
25335 2160 20385 1855 16715 1605
20°C 24470 2355 19410 1990 15740 1755
27°C 22920 2495 18240 2150 14770 1900
Low 188
15°C
23055 1985 18550 1705 15210 1475
20°C 22270 2165 17665 1830 14325 1615
27°C 20860 2295 16600 1975 13440 1745
0.24
in.wg
High
545
15°C
26165 2235 21050 1920 17260 1665
20°C 25270 2440 20045 2060 16250 1815
27°C 23670 2585 18840 2225 15250 1965
Medium 465
15°C
24860 2150 20000 1845 16400 1600
20°C 24010 2345 19045 1980 15440 1745
27°C 22490 2485 17900 2140 14490 1890
Low 141
15°C
22620 1975 18200 1700 14925 1475
20°C 21850 2160 17330 1820 14050 1605
27°C 20465 2285 16290 1970 13185 1740
42QDMT24-718
38QDMT24-718