80
System Heating Performance Data (Cont.)
Ducted Split System
53QDMT42-718 Heat Pump
220-240V/1Ph/50Hz
Indoor Conditions Outdoor Ambient Temperature
ESP
in.wg
Fan
Speed
Air
Flow
cfm
Temp. °C
DB
24/18°C DB/WB 7/6°C DB/WB 2/1°C DB/WB
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
0.36
in.wg
High
1043
15°C
43105 3305 34815 2850 28515 2450
20°C 41775 3600 33155 3060 26855 2690
27°C 39125 3820 31165 3295 25200 2900
Medium 933
15°C
40950 3175 33075 2740 27090 2355
20°C 39690 3460 31500 2940 25515 2585
27°C 37170 3670 29610 3165 23940 2785
Low 263
15°C
37265 2920 30100 2520 24655 2165
20°C 36115 3180 28665 2705 23220 2380
27°C 33825 3375 26945 2915 21790 2565
0.40
in.wg
High
1007
15°C
42480 3290 34310 2835 28100 2440
20°C 41170 3580 32675 3040 26470 2675
27°C 38555 3800 30715 3275 24835 2885
Medium 897
15°C
40360 3160 32595 2725 26695 2345
20°C 39115 3440 31045 2920 25150 2570
27°C 36630 3650 29180 3145 23595 2770
Low 206
15°C
36725 2910 29665 2505 24295 2160
20°C 35595 3165 28250 2685 22885 2365
27°C 33335 3360 26555 2895 21470 2550
42QDMT42-718
38QDMT42-718