89
System Heating Performance Data (Cont.)
Ducted Split System
53QDMT60-518 Heat Pump
380-420V/3Ph/50Hz
Indoor Conditions Outdoor Ambient Temperature
ESP
in.wg
Fan
Speed
Air
Flow
cfm
Temp. °C
DB
24/18°C DB/WB 7/6°C DB/WB 2/1°C DB/WB
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
Capacity
Btu/hr
Input
W
0.36
in.wg
High
1190
15°C
63700 4270 51450 3685 42150 3170
20°C 61740 4670 49000 3965 39700 3500
27°C 57810 4960 46055 4280 37240 3765
Medium 1095
15°C
60515 4100 48880 3540 40045 3045
20°C 58655 4485 46550 3810 37715 3360
27°C 54920 4765 43755 4110 35380 3615
Low 603
15°C
55070 3775 44480 3255 36440 2800
20°C 53375 4125 42365 3505 34325 3095
27°C 49980 4385 39815 3785 32195 3330
0.40
in.wg
High
1159
15°C
62790 4245 50715 3660 41545 3150
20°C 60860 4645 48300 3940 39130 3470
27°C 56980 4935 45395 4255 36705 3745
Medium 1064
15°C
59655 4080 48180 3515 39470 3025
20°C 57820 4460 45885 3785 37175 3335
27°C 54135 4740 43130 4085 34870 3600
Low 578
15°C
54285 3750 43845 3235 35920 2785
20°C 52615 4105 41760 3480 33830 3065
27°C 49260 4360 39245 3760 31735 3310
42QDMT60-718
38QDMT60-518

Table of Contents