EasyManua.ls Logo

Carrier 42KCR009713 - Installation details

Carrier 42KCR009713
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service manual
12
6. Installation details
7.1 Wrench torque sheet for installation
Outside diameter
Torque
mm
inch
Kg.m
φ 6.35
1/4
1.8
φ 9.52
3/8
4.2
φ 12.7
1/2
5.5
7.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
7K
9K
12K
18K
mm
2
1.0
1.0
1.5
2.5
7.3 Pipe length and the elevation
Capacity
Btu/h
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Pipe
length
A (m)
Additional
refrigerant
(g/m)
GAS
LIQUID
5k~9K
3/8’’ (φ 9.52)
1/4’’ (φ 6.35)
5
5
10
30
12K
1/2’’ (φ 12.7)
1/4’’ (φ 6.35)
5
5
10
30
18K
1/2’’ (φ 12.7)
1/4’’ (φ 6.35)
5
8
15
30
Caution:
Capacity is base on standard length and maximum allowance length is base of reliability.
Oil trap should be install per 5-7 meters.
In case that
more than
5m.

Table of Contents