GB - 17
42PQV...S/38VBH...S
ENGLISH
Electrical connections
Notes: 1. Outdoor unit is suitable for outdoor installation.
2. Wire size shown applies to line length up to 15 m.
3. The indoor - outdoor unit interconnecting wires must be A07 RN-F type (245 IEC 57) or higher, with synthetic rubber insulation with
Neoprene coating, according to EN 60335-2-40 codes.
4. The mains supply connecting cable must be H07 RN-F type (245 IEC 57) or higher, with synthetic rubber insuluation with Neoprene coating,
according to EN 60335-2-40 codes.
The mains supply must be connected to the indoor unit.
• Open control box panel (valve cover panel).
• Make electrical connections between units prior to proceeding
to mains supply unit connection.
• Connect the wires to the terminals according to the wiring
diagram and firmly tighten.
• Before proceeding with the unit connection to the mains supply
locate live L and neutral N, then make connections as shown
in the wiring diagram.
• Check that the impedance of the mains power supply is in
conformance with the unit power input indicated on the electric
data table IV.
• Ensure that mains supply connection is made through a switch
that disconnects all poles, with contact gap of a least 3 mm.
• The indoor - outdoor unit interconnecting wires must be
H07 RN-F type (245 IEC 57) or higher, with synthetic rubber
insulation with Neoprene coating, according to EN 60335-2-40
codes.
• The mains supply connecting cable, must be H07 RN-F type
(245 IEC 57) or higher, with synthetic rubber insulation with
Neoprene coating, according to EN 60335-2-40 codes.™
Notes:
1. All field electrical connections are the responsibility of the
installer.
IMPORTANT:
Make ground connection prior to any other electrical
connections.
When disconnecting, disconnect electrical connections before
refrigerant connections.
Table IV: Electrical data
Heat pump A W A W A W A W A mm
2
mm
2
38VBH009S 3.9 852 6.9 1330 4.2 950 7.1 1480 20 1.5 1.5
38VBH012S 5.2 1140 11.2 1850 5.8 1310 11.3 2340 20 1.5 1.5
Indoor-
outdoor
unit
Heating
Cooling
Power input
Main power
connections
(4)
Time-delay
fuse
gL type
Wire size
(2)
Nominal conditions
230V
~
50Hz
ISO 5151.2/T1
indoor 27°C d.b. 19°C w.b.
outdoor 35°C d.b. 24°C w.b.
Peak conditions
198V
~
50Hz
ISO 5151.2/T1
indoor 32°C d.b. 23°C w.b.
outdoor 43°C d.b. 32°C w.b.
Nominal conditions
230V
~
50Hz
ISO 5151.2/High+
indoor 20°C d.b. 15°C w.b.
outdoor 7°C d.b. 6°C w.b.
Peak conditions
198V
~
50Hz
ISO 5151.2/High+
indoor 27°C
outdoor 24°C d.b. 18°C w.b.
Wire size
(2-3)
Never be in contact any other electrical connections with naked refrigerant tube and service valve in order to avoid
electrical connection damage due to hot refrigerant tube.