Operating test, address selector and fault code
Fault code
Once a failure occurs with the indoor unit in operation,
the green or orange LED flashes at intervals of 0.5 seconds.
The fault code is deduced from the number of times the green
LED or orange LED flashes, blocking unit operation.
Between one flash cycle and the next one, a pause of 3 seconds
elapses.
Table V : Fault code
Green LED (indoor unit fault)
Code Description
2 Room air sensor fault
3 Indoor unit coil sensor fault
7 Indoor-outdoor units communication fault
8 Indoor fan motor fault
Continuance Indoor sensor wiring reversed
Orange LED (outdoor unit fault)
Code Description
1 Outdoor sensor fault
2 Indoor-outdoor units mis-matching
3 4way valve fault
4 Outdoor fan motor fault
5 Inverter control fault
6 Power module(IGBT) fault
7 Indoor-outdoor units communication fault
Operating test
Perform the operating test after the units have been installed in
position and the gas leak test has been completed.
Check all electrical connections(instructions and wiring diagram).
Insert the batteries into the remote control and leave it OFF.
Energies the system, turning the power supply ON.
Press the
and buttons of the infrared remote control and
hold them pressed for more than 5seconds.
The display will be cleared, the time segments will display the icon
(Src1=service test).
Press
button to transmit the service test signal to the unit.
After test has been completed, press
button to leave the test
menu.
Note:
When 30 seconds have elapsed and no buttons have been pressed,
the remote control
will automatically exit the test menu and resume its normal operation.
Address selector
If you are installing two indoor units in the same room and you
want them to operate in independent mode, it is necessary to
assign each unit its own address so that each unit can operate via
its own remote control.
For configuration, proceed as follows:
Configuration (of the unit)
Press the
and buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
The display will be cleared, the time segments will display the first
configuration item (rAdr=remote address) and the temperature
segments will display the default value of this configuration item
(Ab=control of both indoor units).
Press either the
or button to change the default value (Ab)
to the new value (A) or (b).
Press
button to transmit the new configuration to the unit.
Press
button to leave the configuration menu.
Configuration (of the remote controller)
Press the
and buttons of the infrared remote control and
hold them pressed for more than 5 seconds.
The display will be cleared, the temperature segments will
display the first configuration item (CH=remote address) and the
time segments will display the default value of this configuration
item (Ab=control of both indoor units).
Press either the
or button to change the default value (Ab)
to the new value (A) or (b).
Press
button to transmit the new configuration to the unit.
Press
button to leave the configuration menu.
Note:
When 30seconds have elapsed and no buttons have been
pressed, the remote control will automatically exit the
configuration menu and the procedure has to be restarted.