37MGHAQ: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
17
Fig. 8 — Clearances - Single Fan Units
Fig. 9 — Clearances - Multiple Fan Units
L
H
118in(3000mm) or more
A
23.6in(600mm)
or more
59in(1500mm)
or more
9.8in(250mm)
or more
9.8in(250mm)
or more
59in (150cm)
or more when
facing each other
Blowing into the air-inlet of other
condenser shall be avoided.
24in (60cm)
or more
59in (150cm)
or more on a
multiple parallel
unit arrangement
24in (61cm) or more on a single parallel unit arrangement
19in (48cm) or more on
a multiple parallel unit
arrangement 4in (10cm)
or more on a single
parallel unit arrangement
9.8in (25cm) or more for proper airflow
24in (61cm) or more is recommended
for service
9.8in (25cm) or more for
proper airflow 24in(61cm)
or more is
recommended
for service