MODE CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
COOL Cooling Configuration COOL_CFG 15
N.CIR Number of Circuits 0 to 3 1 (0307)
2 (0814)
3 (PG16)
2 (2028, PM16)
NUM_CIRC 19
N.A Compressors on Circuit A 1 to 2 1 (PG0324)
1 (PM(1628)
2 PG(28)
A_COMPS 19
MRT.C Compressor Min On Time 120 to 999 sec 180 MIN_ON 19
MOT.C Compressor Min Off Time 300 to 999 sec 300 MIN_OFF 19
RST.C Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S 37
C.DEC Cool Stage Decrease
Time
120 to 999 sec 300 STAGEDEC 18
C.INC Cool Stage Increase Time 120 to 999 sec 450 STAGEINC 18
FOD.C Fanoff Delay, Mech Cool 0 to 600 sec 60 COOL_FOD 18
ALM.N Alert Each Strike No/Yes Yes ALM_NOW 17
SAT Supply Air Temperature 37
SA.PD SAT Cool Demand (+)
Level
0.5 to 10 ^F 1 SAT_POS 21
SA.ND SAT Cool Demand ()
Level
10 to 0.5 ^F 1 SAT_NEG
SAT.U Minimum SAT Upper
Level
35.0 to 65.0 °F 60 (PG0316)
58 (PG 2024)(PM
1628)
53 (PG 28)
SATMIN_H
SAT.L Minimum SAT Lower
Level
35.0 to 65.0 °F 35 (0307)
45 (0814)
50 (PG16)
48 (2028, PM16)
SATMIN_L
SPT Space Temperature 16
CL.PD SPT Cool Demand (+)
Level
0.5 to 5 ^F 1 DEM_POS
CL.ND SPT Cool Demand ()
Level
5 to 0.5 ^F 1 DEM_NEG
C.LAG Cool Thermal Lag Factor 0 to 5 1 COOL_LAG
CIR.A Circuit A 19
CA.LO Circuit A Lockout Temp 0 to 100F °F 0 OATLCMPA
CS.A1 Current Sensing A1 Disable/En
able
Disable (1phase)
Enable (3phase)
A1_SENSE
CS.A2 Current Sensing A2 Disable/En
able
Disable (0324)
Enable (PG 28)
A2_SENSE
A1.FN Level 1 Fans A 0 to 7 no HumidiMiZer
FIOP:
1 (0324)(PM 28)
5 (PG 28)
HumidiMiZer FIOP:
0 (PG0316)
1 (2028, PM16)
CIR_A_1
A2.FN Level 2 Fans A 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
3 (0820)
2 (2428)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (20, PM16)
2 (2428)
CIR_A_2
A3.FN Level 3 Fans A 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
3 (0824)(PM 28)
7 (PG 28)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (2028, PM16)
CIR_A_3
CIR.B Circuit B 19
CB.LO Circuit B Lockout Temp 0 to 100F °F 0: no HumidiMiZer
FIOP
HumidiMiZer FIOP:
40 (PG0816)
0 (2028,
PM16)(0307)
OATLCMPB
CS.B1 Current Sensing B1 Disable/En
able
Disable (0307)
Enable (0828)
B1_SENSE
B1.FN Level 1 Fans B 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
1 (PG0816)
4 (2028, PM16)
HumidiMiZer FIOP:
0 (PG0316)
1 (2028, PM16)
CIR_B_1