MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
COOL (cont) Cooling Configuration       COOL_CFG    
3.ON Fan Lev3 On Temperature 0 to 100 °F no HumidiMiZer FIOP:
65 
HumidiMiZer FIOP:
88 (20, PM16)
68 (2428)(PG0316)
  LEV3ON  
3.OFF Fan Lev3 Off Temperature 0 to 100 °F no HumidiMiZer FIOP:
55
HumidiMiZer FIOP:
78 (20, PM16)
62 (2428)(PG0316)
  LEV3OFF  
HMZR Humidimizer Config       HMZR_CFG    24
REHT Humidimizer Equipped No/Yes   No: no HumidiMiZer
FIOP
Yes: HumidiMiZer FIOP
  REHEAT  24
R.DEC Reheat2 Stage Decr.
Time
0 to 999 secs 60   RSTAGDEC  28
R.INC Reheat2 Stage Incr. Time 0 to 999 secs 300   RSTAGINC  28
RH.FN Reheat Fan Control No/Yes   No (0314)
Yes (1628)
  RHFANCTL  28
RF.LV Reheat ODF Fan On
Level
0 to 3   2 (0320)
3 (2428)
  RHFANLEV  28
RF. ON Reheat ODF Fan On
Temp
0 to 100 °F 75 (PG0316)
93 (PG2024)(PM1628)
85 (PG 28)
  RHFANON  28
RF.OF Reheat ODF Fan Off
Temp
0 to 100 °F 70 (PG0316)
83 (20, PM16)
88 (24)(PM 28)
80 (PG 28)
  RHFANOFF  28
RA.LO Reheat2 OAT Limit A 20 to 70 °F 40   OATLRH_A  28
RA.LP Reheat2 SSP Lo Limit A 50 to 100 psig 80   RHSSPL_A  28
RA.HP Reheat2 SSP Hi Limit A 50 to 100 psig 90   RHSSPH_A  28
RB.LO Reheat2 OAT Limit B,C 20 to 70 °F 50   OATLRH_B  28
RB.LP Reheat2 SSP Lo Limit
B,C
50 to 100 psig 80   RHSSPL_B  28
RB.HP Reheat2 SSP Hi Limit B,C 50 to 100 psig 90   RHSSPH_B  28
HEAT Heating Configuration       HEAT_CFG    15
HT.TY Type of Heat Installed 0=No Heat
1=Gas
2=Electric
  0 (50 series with no elec
tric heat)
1 (48 series)
2 (50 series with electric
heat)
  HEATTYPE  21
N.HTR Number of Heat Stages 1 to 2   1 (48 series 1phase, 50
series <15kW)
2 (48 series 3phase, 50
series >=15kW)
  NUM_HEAT  22
MRT.H Heat Minimum On Time 60 to 999 sec 120   HMIN_ON  22
MOT.H Heat Minimum Off Time 60 to 999 sec 120   HMIN_OFF  22
H.DEC Heat Stage Decrease
Time
120 to 999 sec 300   HSTAGDEC  21
H.INC Heat Stage Increase
Time
120 to 999 sec 450   HSTAGINC  21
FOD.E Fanoff Delay, Elect Heat 10 to 600 sec 30   ELEC_FOD  17
FOD.G Fanoff Delay, Gas Heat 45 to 600 sec 45   GAS_FOD  17
HT.LO Heating Lockout Temp 40 to 125 °F 75   OATLHEAT  21
SAT              15
SAT.H SAT Heat Mode Sensing Disable/En
able
  Disable   SAT_HEAT  
SAM.L Maximum SAT Lower
Level
85 to 200 °F 140   SATMAX_L  
SAM.U Maximum SAT Upper
Level
85 to 200 °F 160   SATMAX_H  
SPT Space Temperature            16
HT.PD SPT Heat Demand (+)
Level
0.5 to 5 ^F 1   HDEM_POS  
HT.ND SPT Heat Demand ()
Level
5 to 0.5 ^F 1   HDEM_NEG  
H.LAG Heat Thermal Lag Factor 0 to 5   1   HEAT_LAG  