APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
CCN CCN CONFIGURATION
→
CCNA CCN Address 1 - 239 CCNADD 1 68
→
CCNB CCN Bus Number 0 - 239 CCNBUS 0 68
→
BAUD CCN Baud Rate 1 - 5 (multi-text strings) CCNBAUDD 3 68
→
BROD CCN BROADCST DEFINITIONS
→
BROD
→
TM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 68
→
BROD
→
OAT.B CCN OAT Broadcast ON/OFF OATBC Off 68
→
BROD
→
ORH.B CCN OARH Broadcast ON/OFF OARHBC Off 68
→
BROD
→
OAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 68
→
BROD
→
G.S.B Global Schedule Broadcst ON/OFF GSBC Off 68
→
BROD
→
B.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 68
→
SC.OV CCN SCHEDULES-OVERRIDES
→
SC.OV
→
SCH.N Schedule Number 0 - 99 SCHEDNUM 1 68
→
SC.OV
→
HOL.T Accept Global Holidays? YES/NO HOLIDAYT No 68
→
SC.OV
→
O.T.L. Override Time Limit 0 - 4 HRS OTL 1 68
→
SC.OV
→
OV.EX Timed Override Hours 0 - 4 HRS OVR_EXT 0 68
→
SC.OV
→
SPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes 69
→
SC.OV
→
T58.O T58 Override Enabled ? YES/NO T58_OVER Yes 69
→
SC.OV
→
GL.OV Global Sched. Override ? YES/NO GLBLOVER No 69
ALLM ALERT LIMIT CONFIG.
→
SP.L.O SPT lo alert limit/occ –10-245 dF SPLO 60 69
→
SP.H.O SPT hi alert limit/occ –10-245 dF SPHO 85 69
→
SP.L.U SPT lo alert limit/unocc –10-245 dF SPLU 45 69
→
SP.H.U SPT hi alert limit/unocc –10-245 dF SPHU 100 69
→
SA.L.O EDT lo alert limit/occ –40-245 dF SALO 40 69
→
SA.H.O EDT hi alert limit/occ –40-245 dF SAHO 100 69
→
SA.L.U EDT lo alert limit/unocc –40-245 dF SALU 40 69
→
SA.H.U EDT hi alert limit/unocc –40-245 dF SAHU 100 69
→
RA.L.O RAT lo alert limit/occ –40-245 dF RALO 60 69
→
RA.H.O RAT hi alert limit/occ –40-245 dF RAHO 90 69
→
RA.L.U RAT lo alert limit/unocc –40-245 dF RALU 40 69
→
RA.H.U RAT hi alert limit/unocc –40-245 dF RAHU 100 69
→
R.RH.L RARH low alert limit 0-100 % RRHL 0 69
→
R.RH.H RARH high alert limit 0-100 % RRHH 100 69
→
SP.L SP low alert limit 0-5 "H2O SPL 0 69
→
SP.H SP high alert limit 0-5 "H2O SPH 2 69
→
BP.L BP lo alert limit –0.25-0.25 "H2O BPL -0.25 69
→
BP.H BP high alert limit –0.25-0.25 "H2O BPH 0.25 69
→
IAQ.H IAQ high alert limit 0-5000 IAQH 1200 69
TRIM SENSOR TRIM CONFIG.
→
SAT.T Air Temp Lvg SF Trim –10 - 10 ^F SAT_TRIM 0 69
→
RAT.T RAT Trim –10 - 10 ^F RAT_TRIM 0 69
→
OAT.T OAT Trim –10 - 10 ^F OAT_TRIM 0 70
→
SPT.T SPT Trim –10 - 10 ^F SPT_TRIM 0 70
→
CTA.T Cir A Sat.Cond.Temp Trim –30 - 30 ^F SCTATRIM 0 70
→
CTB.T Cir B Sat.Cond.Temp Trim –30 - 30 ^F SCTBTRIM 0 70
→
SP.A.T Suct.Press.Circ.A Trim –50 - 50 PSIG SPA_TRIM 0 70
→
SP.B.T Suct.Press.Circ.B Trim –50 - 50 PSIG SPB_TRIM 0 70
→
DP.A.T Dis.Press.Circ.A Trim –50 - 50 PSIG DPA_TRIM 0 70
→
DP.B.T Dis.Press.Circ.B Trim –50 - 50 PSIG DPB_TRIM 0 70
SW.LG SWITCH LOGIC: NO / NC
→
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open 70
→
IGC.L IGC Feedback - Off Open/Close GASFANLG Open 70
→
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 70
→
ECS.L Economizer Switch - No Open/Close ECOSWLOG Open 70
→
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open 70
→
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 70
→
DL2.L Dmd.Lmt.Sw.2 - Dehumid - Off Open/Close DMD_SW2L Open 71
→
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open 71
→
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open 71
→
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open 71
→
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open 71
→
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open 71
DISP DISPLAY CONFIGURATION
→
TEST Test Display LEDs ON/OFF TEST Off 71
→
METR Metric Display ON/OFF DISPUNIT Off 71
→
LANG Language Selection 0-1(multi-text strings) LANGUAGE 0 71
→
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable 71
→
PASS Service Password 0000-9999 PASSWORD 1111 71