APPENDIX A — LOCAL DISPLAY TABLES
MODE — RUN STATUS
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
VIEW AUTO VIEW OF RUN STATUS
→
HVAC ascii string spelling out the hvac modes string 83,84
→
OCC Occupied ? YES/NO OCCUPIED forcible 83,84
→
MAT Mixed Air Temperature dF MAT 83,84
→
EDT Evaporator Discharge Tmp dF EDT 83,84
→
LAT Leaving Air Temperature dF LAT 83,84
→
EC.C.P Economizer Control Point dF ECONCPNT 83,84
→
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 83,84
→
CL.C.P Cooling Control Point dF COOLCPNT 83,84
→
C.CAP Current Running Capacity CAPTOTAL 83,84
→
HT.C.P Heating Control Point dF HEATCPNT 83,84
→
HT.ST Requested Heat Stage HT_STAGE 83,84
→
H.MAX Maximum Heat Stages HTMAXSTG 83,84
ECON ECONOMIZER RUN STATUS
→
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS 84
→
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible 84
→
ACTV Economizer Active ? YES/NO ECACTIVE 84
→
DISA ECON DISABLING CONDITIONS 84
→
DISA
→
UNAV Econ Act. Unavailable? YES/NO ECONUNAV 84
→
DISA
→
R.EC.D Remote Econ. Disabled ? YES/NO ECONDISA 84
→
DISA
→
DBC DBC - OAT Lockout? YES/NO DBC_STAT 84
→
DISA
→
DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT 84
→
DISA
→
DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT 84
→
DISA
→
OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT 84
→
DISA
→
DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT 84
→
DISA
→
EDT EDT Sensor Bad? YES/NO EDT_STAT 84
→
DISA
→
OAT OAT Sensor Bad ? YES/NO OAT_STAT 84
→
DISA
→
FORC Economizer Forced ? YES/NO ECONFORC 84
→
DISA
→
SFON Supply Fan Not On 30s ? YES/NO SFONSTAT 84
→
DISA
→
CLOF Cool Mode Not In Effect? YES/NO COOL_OFF 84
→
DISA
→
OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD 84
→
DISA
→
HELD Econ Recovery Hold Off? YES/NO ECONHELD 84
→
DISA
→
DH.DS Dehumid. Disabled Econ? YES/NO DHDISABL 84
→
O.AIR OUTSIDE AIR INFORMATION 84
→
O.AIR
→
OAT Outside Air Temperature dF OAT forcible 84
→
O.AIR
→
OA.RH Outside Air Rel. Humidity % OARH forcible 84
→
O.AIR
→
OA.E Outside Air Enthalpy OAE 84
→
O.AIR
→
OA.D.T OutsideAir Dewpoint Temp dF OADEWTMP 84
COOL COOLING INFORMATION
→
C.CAP Current Running Capacity % CAPTOTAL 83
→
CUR.S Current Cool Stage COOL_STG 83
→
MAX.S Maximum Cool Stages CLMAXSTG 83
→
DEM.L Active Demand Limit DEM_LIM forcible 83
→
SUMZ COOL CAP. STAGE CONTROL 83
→
SUMZ
→
SMZ Capacity Load Factor % SMZ 83
→
SUMZ
→
ADD.R Next Stage EDT Decrease deltaF ADDRISE 83
→
SUMZ
→
SUB.R Next Stage EDT Increase deltaF SUBRISE 83
→
SUMZ
→
R.PCT Rise Per Percent Capacity RISE_PCT 83
→
SUMZ
→
Y.M IN Cap Deadband Subtracting Y_MINUS 83
→
SUMZ
→
Y.P LU Cap Deadband Adding Y_PLUS 83
→
SUMZ
→
Z.MIN Cap Threshold Subtracting Z_MINUS 83
→
SUMZ
→
Z.PLU Cap Threshold Adding Z_PLUS 84
→
SUMZ
→
H.TMP High Temp Cap Override HI_TEMP 84
→
SUMZ
→
L.TMP Low Temp Cap Override LOW_TEMP 84
→
SUMZ
→
PULL Pull Down Cap Override PULLDOWN 84
→
SUMZ
→
SLOW Slow Change Cap Override SLO_CHNG 84
TRIP MODE TRIP HELPER
→
UN.C.S Unoccup. Cool Mode Start UCCLSTRT 85
→
UN.C.E Unoccup. Cool Mode End UCCL_END 85
→
OC.C.S Occupied Cool Mode Start OCCLSTRT 85
→
OC.C.E Occupied Cool Mode End OCCL_END 85
→
TEMP Ctl.Temp RAT,SPT or Zone CTRLTEMP 85
→
OC.H.E Occupied Heat Mode End OCHT_END 85
→
OC.H.S Occupied Heat Mode Start OCHTSTRT 85
→
UN.H.E Unoccup. Heat Mode End UCHT_END 85
→
UN.H.S Unoccup. Heat Mode Start UCHTSTRT 85
→
HVAC ascii string spelling out the hvac modes string 85
LINK CCN - LINKAGE
→
MODE Linkage Active - CCN ON/OFF MODELINK 85
→
L.Z.T Linkage Zone Control Tmp dF LZT 85
→
L.C.SP Linkage Curr. Cool Setpt dF LCSP 85
→
L.H.SP Linkage Curr. Heat Setpt dF LHSP 85
HRS COMPRESSOR RUN HOURS
→
HR.A1 Compressor A1 Run Hours 0-999999 HRS HR_A1 config 85
→
HR.A2 Compressor A2 Run Hours 0-999999 HRS HR_A2 config 85
→
HR.B1 Compressor B1 Run Hours 0-999999 HRS HR_B1 config 85
→
HR.B2 Compressor B2 Run Hours 0-999999 HRS HR_B2 config 85
STRT COMPRESSOR STARTS
→
ST.A1 Compressor A1 Starts 0-999999 CY_A1 config 85
→
ST.A2 Compressor A2 Starts 0-999999 CY_A2 config 85
→
ST.B1 Compressor B1 Starts 0-999999 CY_B1 config 85
→
ST.B2 Compressor B2 Starts 0-999999 CY_B2 config 85