APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
GENERAL
Occupied ? Yes/No OCCUPIED forcible
Static Pressure "H2O SP
Building Pressure "H2O BP
Outside Air Rel.Humidity % OARH forcible
Return Air Rel.Humidity % RARH forcible
Space Temperature Offset ^F SPTO forcible
Supply Air Setpnt. Reset ^F SASPRSET forcible
Static Pressure Reset SPRESET forcible
IAQ - PPM Return CO2 IAQ forcible
OAQ - PPM Return CO2 OAQ forcible
IAQ Min.Pos.Override % IAQMINOV forcible
GENERIC
20 points dependent upon
the configuration of the
“generics” table in the
Service-Config section on page 128.
HEATING
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Heat Control Type……: ascii text strings
Re-Heat Control Type ascii text strings
Heating Mode………..: ascii text strings
Current Heat Stage HT_STAGE
Heating Control Point dF HEATCPNT
Heat Relay 1 HS1
Heat Relay 2 HS2
Relay 3 W1 Gas Valve 2 HS3
Relay 4 W2 Gas Valve 2 HS4
Relay 5 W1 Gas Valve 3 HS5
Relay 6 W2 Gas Valve 3 HS6
Heat Interlock Relay HIR forcible
Heat Stage 1 Timeguard HS1_TG
Heat Stage 2 Timeguard HS2_TG
Heat Stage 3 Timeguard HS3_TG
Heat Stage 4 Timeguard HS4_TG
Heat Stage 5 Timeguard HS5_TG
Heat Stage 6 Timeguard HS6_TG
MODEDISP
System Mode…………: ascii text strings
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Currently Occupied On/Off MODEOCCP
Timed Override in effect On/Off MODETOVR
DCV resetting min pos On/Off MODEADCV
Supply Air Reset On/Off MODESARS
Demand Limit in Effect On/Off MODEDMLT
Temp.Compensated Start On/Off MODETCST
IAQ pre-occ purge active On/Off MODEIQPG
Linkage Active - DAV On/Off MODELINK
Mech.Cooling Locked Out On/Off MODELOCK
HVAC Mode Numerical Form number MODEHVAC
MODETRIP
Unoccup. Cool Mode Start UCCLSTRT
Unoccup. Cool Mode End UCCL_END
Occupied Cool Mode Start OCCLSTRT
Occupied Cool Mode End OCCL_END
Ctl.Temp RAT,SPT or Zone CTRLTEMP
Occupied Heat Mode End OCHT_END
Occupied Heat Mode Start OCHTSTRT
Unoccup. Heat Mode End UCHT_END
Unoccup. Heat Mode Start UCHTSTRT
HVAC Mode…………..: ascii text strings string
TEMPCTRL
Evaporator Discharge Tmp dF EDT
Leaving Air Temperature dF LAT
Mixed Air Temperature dF MAT
Controlling Return Temp dF RETURN_T forcible
Controlling Space Temp dF SPACE_T forcible