APPENDIX B — CCN TABLES (cont)
CONFIG TABLES (cont)
SERVICE-CONFIG TABLES
TABLE NAME RANGE UNITS POINT NAME DEFAULT
SCHEDOVR
Schedule Number 0-99 SCHEDNUM 0
Accept Global Holidays? Yes/No HOLIDAYT No
Override Time Limit 0-4 hours OTL 1
Timed Override Hours 0-4 hours OVR_EXT 0
Accepting an Override:
SPT Override Enabled ? Yes/No SPT_OVER Yes
T58 Override Enabled ? Yes/No T58_OVER Yes
Allowed to Broadcast a
Global Sched. Override ? Yes/No GLBLOVER No
SET_PNT
Occupied Heat Setpoint 55-80 dF OHSP 68
Occupied Cool Setpoint 55-80 dF OCSP 75
Unoccupied Heat Setpoint 40-80 dF UHSP 55
Unoccupied Cool Setpoint 75-95 dF UCSP 90
Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
Supply Air Setpoint 45-75 dF SASP 55
Supply Air Setpoint Hi 45-75 dF SASP_HI 55
Supply Air Setpoint Lo 45-75 dF SASP_LO 60
Heating Supply Air Setpt 90-145 dF SASPHEAT 85
Tempering Purge SASP –20-80 dF TEMPPURG 50
TABLE NAME RANGE UNITS POINT NAME DEFAULT
ALLM
SPT lo alert limit/occ –10-245 dF SPLO 60
SPT hi alert limit/occ –10-245 dF SPHO 85
SPT lo alert limit/unocc –10-245 dF SPLU 45
SPT hi alert limit/unocc –10-245 dF SPHU 100
EDT lo alert limit/occ –40-245 dF SALO 40
EDT hi alert limit/occ –40-245 dF SAHO 100
EDT lo alert limit/unocc –40-245 dF SALU 40
EDT hi alert limit/unocc –40-245 dF SAHU 100
RAT lo alert limit/occ –40-245 dF RALO 60
RAT hi alert limit/occ –40-245 dF RAHO 90
RAT lo alert limit/unocc –40-245 dF RALU 40
RAT hi alert limit/unocc –40-245 dF RAHU 100
RARH low alert limit 0-100 % RRHL 0
RARH high alert limit 0-100 % RRHH 100
SP low alert limit 0-5 "H2O SPL 0
SP high alert limit 0-5 "H2O SPH 2
BP lo alert limit –0.25-0.25 "H2O BPL -0.25
BP high alert limit –0.25-0.25 "H2O BPH 0.25
IAQ high alert limit 0-5000 IAQH 1200
BP__
Building Press. Config 0-2 BLDG_CFG 0
Power Exhaust Motors 0-2 PWRM 1
0=None,1=4 Mtr, 2=6 Mtr
Building Pressure Sensor Enable/Disable BPSENS Dsable
Bldg Press (+/-) Range 0-1 BP_RANGE 0.25
Building Pressure Setp. –0.25 -> 0.25 "H2O BPSP 0.05
Power Exhaust On Setp.1 0-100 % PES1 35
Power Exhaust On Setp.2 0-100 % PES2 75
Modulating PE Alg. Slct. 1-3 BPSELECT 1
BP PID Evaluation Time 0-10 min BPPERIOD 1
BP Threshold Adjustment 0.1-10 BPZ_GAIN 1
High BP Level 0-1 BPHPLVL 0.05
Low BP Level 0-1 BPLPLVL 0.04
COOL
Capacity Threshold Adjust –10 -> 10 Z_GAIN 1
Compressor Lockout Temp –20 -> 55 dF OATLCOMP 40
Fan-off Delay, Mech Cool 0-600 sec COOL_FOD 60
Minimum Load Valve? Yes/No MLV_SEL No
Motor Master Control ? Yes/No MOTRMAST No
Head Pressure Setpoint 80-150 dF HPSP 110
Enable Compressor A1 Enable/Disable CMPA1ENA Enable
Enable Compressor A2 Enable/Disable CMPA2ENA Enable
Enable Compressor B1 Enable/Disable CMPB1ENA Enable
Enable Compressor B2 Enable/Disable CMPB2ENA Enable
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable
Rev. Rotation Verified ? Yes/No REVR_VER No
Hi SST Alert Delay Time 5-30 min HSSTTIME 10