139
APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
ALARMS01
Active Alarm ascii ALARM_01
------------------------ ascii
Active Alarm ascii ALARM_02
------------------------ ascii
Active Alarm ascii ALARM_03
------------------------ ascii
Active Alarm ascii ALARM_04
------------------------ ascii
follow same format for
ALARMS02
ALARMS03
ALARMS04
ALARMS05
COMPRESR
Compressor A1 Relay On/Off CMPA1
Compressor A1 Feedback On/Off CSB_A1
Curr.Sens.Brd. A1 Status ascii CSBA1ASC
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN config
Comp A1 Locked Out ? Yes/No CMPA1LOK
Compressor A1 Strikes CMPA1STR
Enable Compressor A1 Enable/Disable CMPA1ENA config
Compressor A2 Relay On/Off CMPA2
Compressor A2 Feedback On/Off CSB_A2
Curr.Sens.Brd. A2 Status ascii CSBA2ASC
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN config
Comp A2 Locked Out ? Yes/No CMPA2LOK
Compressor A2 Strikes CMPA2STR
Enable Compressor A2 Enable/Disable CMPA2ENA config
Compressor B1 Relay On/Off CMPB1
Compressor B1 Feedback On/Off CSB_B1
Curr.Sens.Brd. B1 Status ascii CSBB1ASC
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN config
Comp B1 Locked Out ? Yes/No CMPB1LOK
Compressor B1 Strikes CMPB1STR
Enable Compressor B1 Enable/Disable CMPB1ENA config
Compressor B2 Relay On/Off CMPB2
Compressor B2 Feedback On/Off CSB_B2
Curr.Sens.Brd. B2 Status ascii CSBB2ASC
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN config
Comp B2 Locked Out ? Yes/No CMPB2LOK
Compressor B2 Strikes CMPB2STR
Enable Compressor B2 Enable/Disable CMPB2ENA config
DMANDLIM
Active Demand Limit 0-100 % DEM_LIM forcible
Percent Total Capacity 0-100 % CAPTOTAL
Demand Limit Select 0-3 DMD_CTRL config
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Demand Limit Sw.1 Setpt. 0-100 % DLSWSP1 config
Demand Limit Sw.2 Setpt. 0-100 % DLSWSP2 config
4-20 ma Demand Signal 4-20 ma DMDLMTMA forcible
Demand Limit at 20 ma 0-100 % DMT20MA config
CCN Loadshed Signal 0-99 DL_STAT
Loadshed Group Number 0-99 SHED_NUM config
Loadshed Demand Delta 0-60 % SHED_DEL config
Maximum Loadshed Time 0-120 min SHED_TIM config

Table of Contents