91
APPENDIX C: Navigatort Display
MODE -- CONFIGURATIONS (cont)
ITEM EXPANSION VALUES UNITS WRITE STATUS POINT
ECON ECONOMIZER
VNT.C Ventilation Method 0=NONE,
1=ECON,
2=2POS DMPR,
3=ERV,
4=ECON ERV
0: N o FIOP
1: Economi zer FIOP
2: Two Position Damper FIOP
VENTTYPE
FC.MX Free Cooling Max OAT 0to90 °F 65 MAXFREET
EC.MX Econ Max Damper Position 0 to 100 % 100 DAMPMAX
MIN.P MINIMUM POSITION CONFIGS
MP.MX Econ Min at Max Fanspeed 0 to 100 % 30 MINP_MAX
MP.S1 Min Pos --- User Speed 1 0 to 100 % 0 MP_USPD1
MP.D1 M i n P o s --- U s e r P o s 1 0 to 100 % 0 MP_UPOS1
MP.S2 Min Pos --- User Speed 2 0 to 100 % 0 MP_USPD2
MP.D2 M i n P o s --- U s e r P o s 2 0 to 100 % 0 MP_UPOS2
MP.S3 Min Pos --- User Speed 3 0 to 100 % 0 MP_USPD3
MP.D3 M i n P o s --- U s e r P o s 3 0 to 100 % 0 MP_UPOS3
NET NETWORK SETTINGS
BAS BAS Proto col Select 0=NONE,
1=CCN,
2=BACNET
2=BACNET BMS_CFG
NW.TO Network Input Timeout 0 to 600 min 30 NETINTO
CCN CCN
CCN.B CCN Bus number 0 to 239 0 CCNBUS
CCN.A CCN Element Number 1 to 239 1 CCNADD
BAUD CCN Baud Rate 0=9600,
1=19200,
2=38400
2 = 38400 BAUDENUM
BNET BACNET
MAC BACnet Device Macaddress 1 to 127 1 BAC_MAC
BAUD BACnet BMS baud rate 0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
4 = 76800 BAC_BAUD
AUID ALC Auto Id Scheme Yes/No Yes AUID
B.AID BACnet ID Auto ID Yes/No Yes BAC_AUID
ID BACnet ID Number 0 to 4194302 1610101 BAC_ID
DISP DISPLAY SETTINGS
METR Metric Display Yes/No No DISPUNIT
LANG Display Language Select 0=English,
1=Spanish,
2=French,
3=Portuguese
0=English LANGUAGE
PROT User Password Protection Enable/Disable Enable PASS_EBL
PSWD User Password 0 to 9999 1111 PASSWORD