EasyManua.ls Logo

Carrier 48GC Series - User Manual

Carrier 48GC Series
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
1
Controls, Start-- Up, Operation
and Troubleshooting
48/50FC 04---07, 48/50GC 04---06
Single P ackage Rooft op Units
with SystemV u™ Controls Version 1.X
and Puronr (R---410A) Refr ig er ant
C150173
IMPORTANT: This literature covers 48/50FC 04--07 and 48/50GC 04--06 models with SystemVu controls version 1.X (factory--installed
option).
TABLE OF CONTENTS
Page
SAFETY CONSIDERATIONS 2.........................
GENERAL 3.........................................
Conventions Used in This Manual 3......................
BASIC CONTROL USAGE 3...........................
SystemVu Control (factory --installed option) 3..............
SystemVu Interface 3.................................
Accessory Navigatort Display 4........................
System Pilott andTouchPilott Devices 5................
CCN Tables and Display 5.............................
START -- UP 6.........................................
Unit Preparation 6....................................
Refrigerant Service Ports 6.............................
Crankcase Heater 6...................................
Compressor Rotation 6................................
Power Supply 6.....................................
Internal Wiring 6.....................................
Evaporator Fan 6....................................
Condenser Fans and Motors 6...........................
Return--Air Filters 8..................................
Outdoor--Air Inlet Screens 8............................
Accessory Installation 8...............................
Gas Heat (48FC and 48GC) 8...........................
CONTROLS QUICK SET-- UP 8.........................
Control Set Point and Confirmation Log 8.................
Initial Startup 8......................................
Thermostat Control 9.................................
Space T emperature Sensor Control -- Direct Wired
(T--55 or T--56 or T--59) 9.............................
Space Humidistat Control 9............................
Space Relative Humidity Sensor Control 9.................
CCN Communication 9...............................
CCN Linkage Control 9...............................

Table of Contents

Questions and Answers

  • M
    murrayamySep 23, 2025
    What does Alert A110 mean on my Carrier 48GC?
    • G
      Gabriel ColemanSep 23, 2025
      Alert A110 on your Carrier Air Conditioner indicates that the SPT sensor is out of range. This is usually due to a faulty thermistor or an incorrect thermistor caused by improper ohm reading. When this alert is active, cooling and heating will not operate.
  • A
    Ashley GallowayAug 23, 2025
    What does Fault F010 mean on my Carrier 48GC Air Conditioner?
    • A
      Aaron SotoAug 23, 2025
      Fault F010 on your Carrier Air Conditioner indicates a low voltage issue, possibly due to a brownout, low supply voltage, or a missing phase in the supply power. The control system will shut down the unit, but it should automatically clear once the supply voltage rises above 19 volts AC.
  • K
    Karen HoodAug 25, 2025
    What does Fault F011 mean on my Carrier 48GC?
    • D
      Devin JohnsonAug 25, 2025
      Fault F011 indicates that the MBB reference voltage is out of range, usually due to an MBB failure or the supply voltage being out of range. The control system will shut down the unit. This fault should automatically clear when the DC reference voltage returns to its normal range.
  • B
    Brent HarrisonAug 26, 2025
    What does Alert A012 mean on my Carrier 48GC Air Conditioner?
    • S
      solomonstephanieAug 26, 2025
      Alert A012 on your Carrier Air Conditioner signals an MBB zero crossing issue, often caused by an MBB failure or the supply voltage frequency being too high or too low. The alert should automatically clear once the supply voltage returns to the normal range.
  • E
    Edward NealAug 27, 2025
    What does Fault F013 mean on my Carrier 48GC Air Conditioner?
    • P
      Priscilla GriffinAug 28, 2025
      Fault F013 on your Carrier Air Conditioner indicates that MBB Fuse 2 is open, typically due to a wiring error in a switch input or the switch pulling too much current. The control will shut down the unit, but the fault should automatically clear when the fuse temperature returns to normal.
  • C
    christopherbergerSep 18, 2025
    What does Alert A107 mean on my Carrier Air Conditioner?
    • T
      Thomas PhillipsSep 18, 2025
      Alert A107 on your Carrier Air Conditioner indicates that the RAT sensor is out of range. This is usually due to a faulty thermistor, a shorted or open thermistor caused by a wiring error, or a loose connection. When this alert is active, no differential dry bulb crossover control can occur.
  • T
    Timothy CooperSep 15, 2025
    What does Alert A105 mean on my Carrier 48GC Air Conditioner?
    • C
      Corey Kirby DVMSep 15, 2025
      Alert A105 on your Carrier Air Conditioner indicates an open OAT sensor, generally caused by a faulty thermistor or an open thermistor due to a wiring error, or a loose connection. When this alert appears, the economizer will not operate for cooling.
  • M
    Meagan MartinSep 16, 2025
    What does Alert A106 mean on my Carrier Air Conditioner?
    • E
      erica17Sep 16, 2025
      Alert A106 on your Carrier Air Conditioner indicates a shorted OAT sensor, which is typically caused by a faulty thermistor or a shorted thermistor due to a wiring error, or a loose connection. If this alert is active, the economizer will not operate to provide cooling.
  • R
    Robert MorenoSep 6, 2025
    What does Fault F020 mean on my Carrier 48GC?
    • G
      Garrett BellSep 6, 2025
      Fault F020 on your Carrier Air Conditioner indicates a software error, meaning the software on the MBB is not responding. Recovery is automatic if the software can reset the board. If not, try cycling the power to the control before considering board replacement.
  • N
    Nicholas RodriguezSep 3, 2025
    What does Fault F018 mean on my Carrier 48GC?
    • A
      Andrea WestSep 4, 2025
      Fault F018 on your Carrier Air Conditioner indicates an MBB EEPROM failure, meaning the serial EEPROM chip on the MBB, which stores the unit’s configuration, is not responding. Recovery is automatic, but you might need to replace the MBB board. Before replacing the board, try cycling the power to the control.

Summary

Controls, Start-Up, Operation and Troubleshooting

SAFETY CONSIDERATIONS

Information regarding safety precautions during installation and servicing of air-conditioning equipment.

BASIC CONTROL USAGE

Explanation of the SystemVu control system as a comprehensive unit-management system.

START-UP

CONTROLS OPERATION

Indoor Fan Operation

Explanation of how the indoor fan operates under different HVAC modes.

Cooling Operation

Details on the unit's cooling operation, including demand and mode determination.

Heating Operation

Overview of the unit's heating operation, covering gas and electric heat.

SERVICE TEST

Alarm Handling

Faults and Alerts

Information on viewing and clearing unit alarms, including active faults and alerts.

Diagnostic Alarm Codes and Possible Causes

Detailed list of diagnostic alarm codes and their probable causes.

MAJOR SYSTEM COMPONENTS

UNIT START-UP CHECKLIST

Carrier 48GC Series Specifications

General IconGeneral
Voltage208/230V
Energy Efficiency Ratio (EER)Up to 12.5
RefrigerantR-410A
Operating Voltage208/230 V
Gas Heating Input60, 000 - 150, 000 BTU/h
Cooling Capacity2 - 5 Tons
Heating Capacity60, 000 - 150, 000 BTU/h