EasyManua.ls Logo

Carrier 48HD008 - INSTALLATION - PIPING AND WIRING; Gas Piping and Electrical Connections

Carrier 48HD008
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Spreader
bars
are
not
required
if
top
crating
is
left
on
unit.
Rollers
may
be
used
to
move
unit
across
a
roof.
Level
by
using
unit
frame
as
a
reference,
leveling
tolerance
is
±
1/16
in.
per
linear
foot
in
any
direction.
See
Fig.
2
for
additional
information.
Weight
is
shown
in
Table
1.
Lifting
holes
are
provided
in
base
rails
as
shown
in
Fig.
2.
Refer
to
rigging
instructions
on
unit.
POSITIONING
Maintain
clearance
around
and
above
unit
to
provide
minimum
distance
from
com¬
bustible
materials,
proper
airflow
and
service
access.
See
Fig.
3
and
4.
Do
not
install
unit
in
an
indoor
location.
Do
not
locate
unit
air
inlets
near
exhaust
vents
or
other
sources
of
contaminated
air.
Although
unit
is
weatherproof,
guard
against
water
from
higher
level
runoff
and
overhangs.
Locate
mechanical
draft
system
flue
assembly
at
least
48
in.
from
any
opening
through
which
com¬
bustion
products
could
enter
the
building,
and
at
least
48
in.
from
an
adjacent
building.
When
unit
is
located
adjacent
to
public
walkways,
Hue
assembly
must
be
at
least
7
ft
above
grade.
After
unit
is
in
position,
remove
polyethylene
shipping
wrapper
and
rigging
skids.
Step
4
Install
Flue
Hood
Flue
hood
and
screen
are
shipped
screwed
to
the
basepan
in
furnace
compartment.
Remove
from
shipping
location
and
using
screws
provided,
install
flue
hood
and
screen
in
location
shown
in
Fig.
3
or
4.
On
48LDT004-006
units,
a
flue
restrictor
plate
MUST
be
assembled
to
the
flue
discharge.
The
plate
is
shipped
with
the
flue
hood
package.
Install
as
shown
in
Fig.
5.
Step
5
Trap
Condensate
Drain
See
Fig.
3
or
4
for
drain
location.
A
7/
8-in.
preformed
drain
hose
is
shipped
clamped
to
the
indoor
basepan.
At
instal¬
lation,
re-route
the
hose
so
it
passes
through
the
hole
in
the
indoor
basepan
and
unit
base
rail.
When
installed
properly,
the
hose
protrudes
through
the
base
rail
one
inch.
Replace
clamp
over
the
hose
where
hose
passes
through
the
basepan
to
ensure
that
hose
remains
level.
Use
a
trap
at
least
4
in.
deep
and
provide
protection
for
trap
against
freeze-up.
Step
6
Install
Gas
Piping
Unit
is
equipped
for
use
with
type
of
gas
shown
on
nameplate.
Refer
to
local
building
codes,
or,
in
the
absence
of
local
codes,
to
ANSI
Z223.1-1980
entitled
National
Fuel
Gas
Code.
Natural
gas
pressure
at
unit
gas
connection
must
not
be
less
than
5
in.
wg
or
greater
than
13.5
in.
wg
while
unit
is
operating.
Size
gas
supply
piping
for
0.5in.wg
maximum
pressure
drop.
Do
not
use
supply
pipe
smaller
than
unit
gas
connection.
See
Fig.
6
for
typical
pipe
guide
and
location
of
external
manual
main
shutoff
valve.
For
LP
gas
units,
pressure
at
unit
gas
connection
must
not
be
less
than
12
in.
wg
or
greater
than
13.5
in.
wg.
A
1
/
8-in.
N
PT
plugged
tapping,
accessible
for
test
gage
connection,
must
be
installed
immediately
up¬
stream
of
the
gas
supply
connection
to
the
furnace.
Step
7
Make
Electrical
Connections
FIELD
POWER
SUPPLY
004,005,006,007
All
units
except
208/230-volt
units
are
factory
wired
for
the
voltage
shown
on
the
nameplate.
If
the
208/230-v
unit
is
to
be
connected
to
a
208
power
supply,
the
transformer
must
be
re¬
wired
by
connecting
the
blue
wire
to
C-13
and
the
red
wire
to
C-DUL
48HDD,LDD/HD,LD008
230-
and
460-volt
units
are
factory
wired
for
the
voltage
shown
on
nameplate.
If
unit
will
be
connected
to
a
208
power
supply,
the
transformer
must
be
rewired
by
connect¬
ing
the
black
wire
to
the
200-volt
lead
and
insulating
the
230-volt
lead.
48HHD,LHD/HH,LH008
230-
and
460-volt
units
are
factory
wired
for
the
voltage
shown
on
nameplate.
If
208/
230-volt
unit
will
be
connected
to
a
208
power
supply,
the
transformer
must
be
rewired
by
connecting
the
blue
wire
to
C-13
and
red
wire
to
C-DUL
All
Units
Refer
to
unit
label
diagram
for
addi¬
tional
information.
Pigtails
are
provided
for
field
service.
Use
factory-supplied
splices
or
UL-
approved
copper/aluminum
connector.
When
installing
units,
provide
a
disconnect
per
NEC.
All
field
wiring
must
comply
with
National
Elec¬
trical
Code
and
local
requirements.
Install
conduit
connectors
in
side
panel
openings
indicated
in
Fig.
3
or
4.
Route
power
lines
through
connector
to
terminal
connections
as
shown
in
Fig.
7.
Voltage
to
compressor
terminals
during
opera¬
tion
must
be
within
voltage
range
indicated
on
unit
nameplate
(also
see
Table
2).
On
3-phase
units,
voltages
between
phases
must
be
balanced
within
2%
and
the
current
within
10%.
Use
the
formula
shown
in
Table
2,
Note
2
to
determine
the
%
voltage
imbalance.
Contact
local
power
company
for
cor¬
rection
of
improper
voltage
or
phase
imbalance.
Operation
on
improper
line
voltage
or
excessive
phase
imbalance
constitutes
abuse
and
may
cause
damage
to
electrical
components.
Such
operation
would
invalidate
any
applicable
warranty.
FIELD
CON
I
ROL
WIRING
Install
a
Carrier-
approved
accessory
thermostat
assembly
according
to
installation
instructions
included
with
the
acces¬
sory.
Locate
thermostat
assembly
on
a
solid
wall
in
the
conditioned
space
to
sense
average
temperature.
3

Related product manuals