APPENDIX C: Navigatort Display
MODE -- CONFIGURATIONS (cont)
ITEM EXPANSION RANGE UNIT DEFAULT POINT
ALM.O Alarm Relay Config Menu
ALM.C ALM Relay Assigned Chan 0=NONE,
1=MBB RLY11,
2=MBB RLY06
1=MBB RLY11 ALM_CHAN
A.TST Thermost at Alerts Ye s/No Yes TSTAT_AL
A.HW Hardware failures Alerts Yes/No Yes HW_AL
A.SRT SAT/RAT Sensor Alerts Yes/No Yes SATRATAL
A.OAT OAT Thermistor Alerts Yes/No Yes OATRL_AL
A.SPT Space Sensors Alerts Yes/No Yes SPACE_AL
A.TRN Transducer Sensor Alerts Yes/No Yes TRANS_AL
A.RH RH sensor failure Alert Yes/No Yes RHS_AL
A.CO2 Air Quality CO2 Alerts Yes/No Yes CO2S_AL
A.OAC OACFM Alarm Relay Ye s/No Yes OACFM_AL
A.ECO Economizer Alerts Yes/No Yes ECON_AL
A.FIL Dirty Filter Alert s Yes/No Yes FILT_AL
A.GEN General Status Alerts Yes/No Yes GENS_AL
A.CKT Refrig Circuit Alerts Yes/No Yes CKT_AL
A.CMP Compressor Alerts Yes/No Yes COMP_AL
A.HT Heating failure Alerts Yes/No Yes HEAT_AL
A.FAN Indoor Fa n Alerts Yes/No Yes FAN_AL
A.IOB Relay On Active IOBA Yes/No Yes IOBFA_AL
A.FAU Relay on Active Faults Yes/No Yes FAULT_AL
CAL Calibration Menu
T. O AT OAT Sensor Trim Offset --- 10 t o 10 °F 0 OAT_TRIM
T. R AT RAT Sensor Trim Offset --- 30 to 30 °F 0 RAT_TRIM
T. F S T FST Sensor Trim Offset --- 10 to 10 °F 0 FST_TRIM
T. S P T SPT Sensor Trim Offset --- 30 to 30 °F 0 SPT_TRIM
T. S T O SPTO Sensor Trim Offset --- 1 t o 1 °F 0 SPTOTRIM
T. S R H SPRH Sensor Trim Offset --- 15 to 15 % 0 SPRHTRIM
T. I A Q IAQ sensor Trim Offset --- 200 t o 200 ppm 0 IAQ_TRIM
T. O A Q OAQ Sensor Trim Offset --- 200 to 200 ppm 0 OAQ_TRIM
T. O R H OARH Sensor Trim Offset --- 15 to 15 % 0 OARH TRIM
T.RRH RARH Sensor Trim Offset --- 15 t o 15 % 0 RARHTRIM
T. S P.A Cir.A SSP Sensor Trim --- 50 to 50 psig 0 SSPATRIM
T. D P. A Cir.A SDP Sensor Trim --- 50 t o 50 psig 0 SDPATRIM
T. E C O Econ Fdback Trim Offset --- 15 to 15 % 0 EC1DTRIM
OCF.T OACFM Sensor Trim Offset --- 10 t o 10 °F 0 OCFMTRIM
NET Building Net Config Menu
BAS BAS Protocol Select 0=NONE,
1=CCN,
2=BACNET
0=NONE BMS_CFG
NW.TO Network Input Timeout 0 to 600 min 30 NETINTO
CCN CCN Network Config Menu
CCN.B CCN Bus Number 0 to 239 0 CCNBUS
CCN.A CCN Element Number 1 t o 239 1 CCNADD
BAUD CCN Baud Rate 0=9600,
1=19200,
2=38400
2 BAUDENUM
B.ACK CCN Broadcast Ack’er Ye s/No No CCNBCACK
B.GS Global Schedule Broadcst Ye s/No No CCN_GSBC
B.TIM CCN Time Broadcast Ye s/No No CCNBC
B.OAT Broadcast OAT On Network Yes/No No OATBC
B.ORH Broadcast OARH On Netwrk Ye s/No No OARHBC
B.OAQ Broadcast OAQ On Network Yes/No No OAQBC
B.IAQ Broadcast IAQ On Network Ye s/No No IAQBC
DEV.L Device Location text string <blank> DEV_LOC
REF.N Reference number text string <blank> REF_ NUM
BNET BACnet Config menu
MAC BACnet Device Macaddress 1 to 127 01 BAC_MAC
BAUD BACnet BMS baud rate 0=9600,
1=19200,
2=38400,
3=57600,
4=76800,
5=115200
4=76800 BAC_BAUD
AUID ALC Auto Id Scheme Yes/No Yes AUID
B.AID BACnet ID Auto ID Ye s/No Yes BAC_AUID
ID BACnet ID Number 0 to 4194302 1610101 BAC_ID