APPENDIX E: BACnet Points List (cont)
Point Name Typ e
BACnet
Object ID
Alias
(CCN Point Name)
BACnet Object Name
A161--- OARH Short Circuit Alert BMBV BV:208 a_shtoarh
A162--- RARH Open Circuit Alert BMBV BV:199 a_opnrarh
A163--- RARH Short Circuit Alert BMBV BV:210 a_shtrarh
A164--- IAQ Open Circuit Alert BMBV BV:194 a_opniaq
A165--- IAQ Short Circuit Alert BMBV BV:205 a_shtiaq
A166--- OAQ Open Circuit Alert BMBV BV:195 a_opnoaq
A167--- OAQ Short Circuit Alert BMBV BV:206 a_shtoaq
A168 SPRH Open Circuit Alert BMBV BV:274 a_opnsrh
A169 SPRH Short Circuit Alert BMBV BV:275 a_shtsrh
A170--- Damper feedbck out of Range BMBV BV:184 a_badec1
A171--- Damper Feedback Open Circuit Alert BMBV BV:192 a_opnec1
A172--- Damper Feedback Short Circuit Alert BMBV BV:203 a_shtec1
A190--- Thermostats Simultaneous Heat Cool Alert BMBV BV:223 a_simhc
A191--- Thermostat Improper Cool Alert BMBV BV:220 a_impcl
A192--- Thermostat Improper H eat Alert BMBV BV:221 a_impht
A203--- Dirt y Filter Alert BMBV BV:214 a_dfilt
A210--- General Status Alert BMBV BV:244 a_gensw
A312--- Circuit A Unexpected Off Alert BMBV BV:181 a_caoff
A313--- Circuit A Hi Discharge Pressure Alert BMBV BV:172 a_cahdp
A314--- Circuit A Hi Pressure Switch Alert BMBV BV:171 a_cahps
A315--- Circuit A Low Discharge Pressure Alert BMBV BV:236 a_caldp
A316--- Circuit A Low System Pressure Alert BMBV BV:170 a_calsp
A317--- Circuit A Press Ratio Alert BMBV BV:169 a_capr
A320--- Compressor A1 Reverse Rotation Alert BMBV BV:179 a_ca1rr
A321--- Comp A1 Fail to Pressurize Alert BMBV BV:182 a_ca1ftp
A323--- Comp A2 Rev Rotation Alert BMBV BV:174 a_ca2rr
A324--- Comp A2 Fail to Pressurize Alert BMBV BV:177 a_ca2ftp
A410--- IGC Ignition Failure Alert BMBV BV:222 a_ noign
A510--- Indoor Fan status Alert BMBV BV:219 a_idfwar
A603--- IDF VFD in Hand Alert BMBV BV:227 a_vfdhnd
A605--- IDF VFD Thermal Warning Alert BMBV BV:239 a_vfdtwa
A606 --- IDF VFD Voltage Warning Alert BMBV BV:240 a_vfdvwa
A607--- VFD Current limit Warning Alert BMBV BV:238 a_vfdcwa
A608--- IDF VFD Warning Alert BMBV BV:228 a_vfdwar
A700--- Economizer Not Modulating Alert BMBV BV:215 a_dnm
A701--- Economizer Damper Stuck Closed Alert BMBV BV:216 a_dnm_sc
A702--- Economizer Damper Stuck Open Alert BMBV BV:217 a_dnm_so
A703---Econ omi zer Actu ator Mech an i cal ly Dis con n ec ted Alert BMBV BV:218 a_dnmemd
A710--- Economizer Not Cooling Alert BMBV BV:224 a_t24enc
A711--- Economizer Improper Cooling Alert BMBV BV:226 a _ t 24ew c
A712--- Excess Outside Air Alert BMBV BV:225 a_t24eoa
Adaptive Staging Config BMBV BV:115 adptstat
alarm_reset BMBV BV:33 alarm_reset
Alarm Reporting Enable BMBV BV:27 alarmen
ALC Auto Id Scheme BMBV BV:106 auid
All Heat Stages Locked out BMBV BV:122 allhtloc
Auto Heat test BMBV BV:161 autoheat
BACnet BMS Schedule BMBV BV:108 bms_sced
BACnet ID Auto/Manual BMBV BV:107 bac_auid
Calendar Object Status BMBV BV:110 calobjst
Circuit A CMP A1 Loader BMBV BV:9 cmpalena
Circuit A Compressor 1 BMBV BV:5 cmpa1ena
Circuit A Compressor 2 BMBV BV:6 cmpa2ena
Circuit A high Pressure Switch BMBV BV:4 circa_hps
Circuit A Lockout BMBV BV:128 ciralock
Clear Alarm History BMBV BV:32 alarm_hist_clear
CMP A1 Bump Test Request BMBV BV:71 s_bmpa1
CMP A1 Cool Test Request BMBV BV:74 s_coola1
CMP A2 Bump Test Request BMBV BV:72 s_bmpa2
CMP A2 Cool Test Request BMBV BV:75 s_coola2
CMP AL Bump Test Request BMBV BV:64 s_bmpald
CMP AL Cool Test Request BMBV BV:79 s_cola1d
COFS Discrete Input BMBV BV:7028 cofs condensate_switch
Compressor A1 Available BMBV BV:123 ca1_aval
Compressor A1 Locked Out BMBV BV:124 ca1_lock