150
APPENDIX E: BACnet Points List (cont)
Point Name Typ e
BACnet
Object ID
Alias
(CCN Point Name)
BACnet Object Name
Compressor A2 Available BMBV BV:125 ca2_aval
Compressor A2 Locked Out BMBV BV:126 ca2_lock
Compressor Cooling Ok BMBV BV:302 okmechcl
Cooling Liquid Valve CirA BMBV BV:7052 clv_a
cooling liquid valve Relay Test BMBV BV:456 s_clv_a
Cooling Liq Valve CirA Enable BMBV BV:7049 clva_en
Crankcase Heater Relay 1 BMBV BV:3 cch_relay
Damper Position Error BMBV BV:21 dmpr_err
Damper Status Good BMBV BV:39 damp_good
Daylight Savings Enable BMBV BV:93 dst_cfg
Daylight Savings time Active BMBV BV:92 dst_actv
DD IDF High Speed Relay BMBV BV:448 fspdhrly
DD IDF Low Speed Relay BMBV BV:446 fspdlrly
DD IDF Med. Speed Relay BMBV BV:447 fspdmrly
Diff Bulb Lock Out BMBV BV:40 db_lock_out
Differential Dry Bulb Enable BMBV BV:41 diffbulb dif_db_ena
Differential Enthalpy Enable BMBV BV:42 dif_enth_ena
Economizer Installed BMBV BV:131 econo_cfg
Enthalpy Lockout BMBV BV:44 enthlock enth_lock_out
equip_alarm BMBV BV:7048 equip_alarm
F010--- MBB low voltage Fault BMBV BV:270 f_mbblov
F011---MBB Reference voltage Fault BMBV BV:271 f_mbbref
F013--- MBB Fuse 2 Open Fault BMBV BV:268 f_mbbf2
F014--- MBB Fuse 3 Open Fault BMBV BV:269 f_mbbf3
F018--- MBB EEPROM Read/Write Failure Fault BMBV BV:267 f_mbbeep
F20--- Softw are Error Fault BMBV BV:243 f_bad_dd
F200--- Fire Shutdown Fault BMBV BV:242 f_fire
F201--- Condensate Overflow Fault BMBV BV:273 f_cofs
F202--- Freeze Protection Fault BMBV BV:264 f_freeze
F204--- Remote Shutdown Fault BMBV BV:272 f_remoff
F211 --- General Status Fault BMBV BV:265 f_gensw
F310--- Circuit A Down Due To Failure Fault BMBV BV:168 f_caddf
F311--- Circuit A Low Charge Fault BMBV BV:167 f_caloch
F318--- Compresso r Stuck on Fault BMBV BV:241 f_cstuck
F319--- Compressor A1 Down due to Failure Fault BMBV BV:178 f_ca1ddf
F322 --- Comp A2 Down Fail Fault BMBV BV:173 f_ca2ddf
F411 --- Rollout without Heating BMBV BV:235 f_ronoht
F412--- Run Away Heat Fault BMBV BV:266 f_hstuck
F511--- IDF off when comand on Fault BMBV BV:230 f_idfoff
F512---IDFOnWhenComandedOff BMBV BV:231 f_idfon
F600--- IDF VFD Communication Error Fault BMBV BV:229 f_idfcom
F601--- IDF VFD Unexpected Fa ult BMBV BV:253 f_vfdune
F602--- IDF VFD Lockout Fault BMBV BV:234 f_vfdlo
F604--- IDF VFD in Hand Fault BMBV BV:233 f_vfdhnd
F611--- IDF VFD Earth Fault BMBV BV:255 f_vfdef
F612--- IDF VFD Control Word Fa ult BMBV BV:254 f_vfdcf
F613--- IDF VFD Over Current Fault BMBV BV:259 f_vfdoc
F614--- IDF VFD Over Temperature Fault BMBV BV:249 f_vfdot
F615--- IDF VFD Inverter Overload Fault BMBV BV:260 f_vfdol
F616--- IDF VFD Under Voltage Fault BMBV BV:263 f_vfduv
F617--- IDF VFD Over Voltage Fault BMBV BV:261 f_vfdov
F618--- IDF VFD Short Circuit Fault BMBV BV:262 f_vfdsc
F619--- IDF VFD Main Phase Loss Fault BMBV BV:258 f_vfdmpf
F620--- IDF VFD Phase U Loss Fault BMBV BV:250 f_vfdpul
F621--- IDF VFD Phase V Loss Fault BMBV BV:251 f_vfdpvl
F622--- IDF VFD Phase W Loss Fault BMBV BV:252 f_vfdpwl
F623--- IDF VFD Control V oltage Fault BMBV BV:256 f_vfdivl
F624--- IDF VFD Supply VDD Low Fault BMBV BV:257 f_vfdlve
FanOnWhenOccupied BMBV BV:46 fanon_oc occupied_fan
Fan shutdown on failure BMBV BV:7008 fatalfan sfan_fail_alarm
FBD SAT locked out BMBV BV:439 fbdsatlo
FBD SST locked out BMBV BV:440 fbdsstlo
Filter Status Switch BMBV BV:1016 flt_status
Fire Shutdown Switch BMBV BV:112 firedown
Free Cooling Available BMBV BV:65 okfreecl ok_free_cl