155
Settings -- Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point Entry
SWITCH INPUTS CONFIGS (cont) DI Config Menu
REM.SHUTDOWN CHAN Remote Shutdown Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ROFFCHAN
REM.SHUTDOWN SW T Remote Shutdown Sw Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ROFF_CFG
REM.SHUTDOWN TYPE Remote Shutdown ALM Type 0=Normal,
1=Emergency
0=Normal ROFFTYPE
COFS CHANNEL COFS Assigned Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None COFSCHAN
COFS TYPE COFS Switch Ty pe 0=NORM OPEN,
1=NORM CLSD
1=NORM CLSD COFS_CFG
GEN STATUS CHAN General Status Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None GEN_CHAN
GEN STAT SW TYPE General Status Sw Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN GENS_CFG
SHUTDOWN GEN STAT General Status shutdown? Ye s/No Yes GENFATAL
ENTHALPY SW CHAN Enthalpy Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04
0=None ENTHCHAN
ENTHALPY SW TYPE Enthalpy Switch Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ENTH_CFG
ANALOG INPUT CONFIGS Analog Inputs Configuration Menu
IAQ SENSOR CHAN IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0: no FIOP
1: FIOP
IAQ_CHAN
SPRH SENS CHANNEL SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
4=SIOB AI10
0=None SPRHCHAN
SPRH RH @ 4MA SPRH Sensor Value at 4mA 0 to 100 % 0 SPRH_4MA
SPRH RH @ 20MA SPRH Sensor Value @ 20mA 0 to 100 % 1 SPRH20MA
IAQ PPM @ 4MA IAQ Sensor Value at 4mA 0 to 5000 ppm 0 IAQ_4MA
IAQ PPM @ 20MA IAQ Senso r Value at 20mA 0 to 5000 ppm 2000 IAQ_20MA
OAQ SENSOR CHAN OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN
OAQ PPM @ 4MA OAQ Sensor Value at 4mA 0 to 5000 ppm 0 OAQ_4MA
OAQ PPM @ 20MA OAQ Sensor Value at 20mA 0 to 5000 ppm 2000 OAQ_20MA
OARH SENSOR CHAN OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
n/a 0: no Enthalpy FIOP
3: Enthalpy FIOP
OARHCHAN
OARH RH @ 4MA OARH Sensor Value at 4mA 0 to 100 % 0 OARH_4MA
OARH RH @ 20MA OARH Sensor Val. a t 20mA 0 to 100 % 100 OARH20MA
RARH SENS CHANNEL RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
n/a 0=None RARHCHAN
RARH RH @ 4MA RARH Sensor Value at 4mA 0 to 100 % 0 RARH_4MA
RARH RH @ 20MA RARH Sensor Value @ 20mA 0 to 100 % 100 RARH20MA
OACFM SENSOR CHAN OACFM Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
n/a 0=None OCFMCHAN
OACFM @ 4MA OACFM value at 4mA 0 to 100 CFM 0 OCFM_4MA
OACFM @ 20MA OACFM Value @ 20mA 0 to 100 CF M 20 OCFM20MA
COOLING Cooling Configurations Menu
COOLING STAGE QTY Number of Cooling Stages 0to3 3 NUMCSTGS
L OW COOL COMP Low Cool Compressor 1to2 1 LC_COMP
COMP MIN ON TIME Compressor Min On Time 180 to 600 sec 300 C_MINON
COMP MIN OFF TIME Compressor Min Off Time 120 to 600 sec 180 C_MINOFF
STRIKE CLEAR TIME Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
COOL STAGEUP TIME Cool Stage Increase Time 120 to 999 sec 450 CSTAGINC
COOL SATTREND LEV Cooling SAT Trend Level --- 1 . 0 t o 1 . 0 ^F/min --- 0 . 2 SAT_TLC
UPPER MIN SAT Cool Min SAT Upper Level 35.0 to 65.0 °F 56 (sizes 04--- 06)
53 (sizes 07 --- 12)
56 (sizes 14 --- 26)
SATMIN_H