Settings -- Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point Entry
COOLING (cont) Cooling Configurations Menu
LOWER MIN SAT Cool Min SAT Lower Level 35.0 to 65.0 °F 46 (sizes 04--- 06)
42 (sizes 07 --- 12)
46 (sizes 14 --- 26)
SATMIN_L
SPRH DEADBAND Space RH Deadband 0 % 5 SPRH_D8
HUMZ LOCKOUT OAT Humidimizer Lockout Temp ---20 to 75 °F 40 OATLHUMZ
COOL FANOFF DELAY Cooling Fan---off Delay 0 to 600 sec 75 COOL_FOD
FBD TYPE FBD CONTROL TYPE 0=None,
1=Comfort,
2=Max
0=None FBD_TYPE
FBD SAT MIN VALUE FBD SAT MIN VALUE 35 to 80 °F 46 FBDH_SAT
FBD LOW SP FBD LOW SP --- 2 0 t o 0 °F delta --- 2 . 5 FBDLO_SP
FBD SST MIN VALUE FBD SST MIN VALUE 10 to 60 °F 32 FBDH_SST
LOW AMBIENT LOW AMBIENT CONFIGS MENU
CIR.A LOCKOUT OAT CircuitALockoutTemp ---20 to 75 °F 0: no Economizer FIOP
40: Economizer FIOP
OATLCMPA
LOW AMBIENT TEMP Low Ambient Temperature 0to80 °F 66 LA_TEMP
LOW COOL MIN OAT Low Cool lockout Temp --- 20 to 60 °F 10 (sizes 04--- 06)
30 (sizes 07 --- 12)
40 (sizes 14 --- 26)
LCLOCKSP
MED COOL MIN OAT Medium Cool lockout Temp --- 20 to 60 °F 20 (sizes 07--- 12)
30 (sizes 14 --- 26)
MCLOCKSP
LA DEHUM LEV 1 Low Ambient Dehum Lev 1 40 to 125 °F 80 LAHTEMP1
LA DEHUM LEV 2 Low Ambient Dehum Lev 2 40 to 125 °F 61 LAHTEMP2
LA DEHUM LEV 3 Low Ambient Dehum Lev 3 40 to 125 °F 55 LAHTEMP3
LA DEHUM SDT SP 1 LA Dehum SDT SP Lev 1 60 to 120 °F 82 LHSDTSP1
LA DEHUM SDT SP 2 LA Dehum SDT SP Lev 2 60 to 120 °F 93 LHSDTSP2
LA DEHUM SDT SP 3 LA Dehum SDT SP Lev 3 60 to 120 °F 104 LHSDTSP3
HUMZ ENABLE Humidimizer Status Yes/No enum No for all except
Humidimizer units
HUMZ_EN
RDVA ENABLE Reheat Dischg Valve CirA Ye s/No enum No for all except
Humidimizer units
RDVA _EN
RLVA ENABLE Reheat Liquid V alv e CirA Yes/ No enum No for all except
Humidimizer units sizes
04--- 06
RLVA _E N
CLVA ENABLE Cooling Liq V alve CirA Yes/No enum No for all except
Humidimizer units sizes
04--- 06
CLVA_EN
LDVA ENABLE Liqu id Diver t V alv e CirA Yes/No enum No for all except
Humidimizer units sizes
07--- 26
LDVA_EN
CHARGE DIAGNOSTICS Refriger an t Char g e Diagnos t ic Config Menu
LOW CHARGE LEVEL Low Refrig Charge Level 0 to 150 psi 50 LOCHARGE
NO LOW CHARGE OAT Low Charge Disable Temp ---40 to 50 °F 10 LOCH_LOT
CIR.A SDP LIMIT CirA High Pressure Limit 400 to 700 psig 600 HIPLIM_A
LOW DISCHARGE LEV Low Discharge Level 5.0 to 20.0 °F 7 SDTLEV
MIN PRESS RATIO Minimum pressure ratio 0.00 to 5.00 1.35 MINPSI_R
LOW SUCTION DIAG. Low Suction Diagnostic Config Menu
LOW SUC OK TEMP Suction OK Temperature 10.0 to 50.0 °F 18 SSTOK
LOW SUC LEVEL 1 Low Suction Level 1 Temp 10.0 to 50.0 °F 20 SSTLEV1
LOW SUC LEVEL 2 Low Suction Level 2 Temp 5.0 to 50.0 °F 15 SSTLEV2
LOW SUC LEVEL 3 Low Suction Level 3 Temp 0.0 to 50.0 °F 10 SSTLEV3
LO SUC DIAG DELAY Delay On Low SST Check 0 to 300 sec 0 SSTCKDLY
COMPRESSOR TRANSISTION Compressor Transition diagnostic config
menu
COMP L2 DIAG DLY Comp level 2 diag delay 1to99 sec 15 (sizes 04 --- 12)
40 (sizes 14 --- 26)
CDDTLEV2
IAG. COMP OFF Diag Comp Unexpected Off Enable/Disable Enable CD_UEOFF
CIR STUCK ON D IAG Ci rcuit Stuck On Diag. Enable/Disable Enable DCKTOFF
CIR.A MIN DIS.P Min discharge change 0 to 99.0 psi 11 (sizes 04--- 12)
17 sizes 14--- 26)
MDP_DISA
CIR.A MIN SUC.P Min Suction change 0 to 99.0 psi 4 ( s i z e s 0 4 --- 0 6 )
6.5 (size 07)
8 (size 08)
7 ( s i z e s 0 9 --- 1 2 )
14 (sizes 14 --- 26)
MDP_SUCA
OFF P.RATIO CirA P.Ratio off change ---1.00 to 1.00 --- 0.2 (sizes 04--- 06, 07,
09--- 14)
--- 0.3 (sizes 08, 17--- 26)
OFFPR_A
ODF SETTINGS Outdoor Fans Configurations Menu
ODF SIGNAL QTY Number of ODF Outputs 0to3 1 ( s i z e s 0 4 --- 0 6 )
2 (sizes 07,17, or 20)
3 (sizes 08--- 14, 24---26)
NUM_ODF
ODF LOW COOL SPD ODF Low Cool Speed 0 to 1200 rpm 1000 (size 04)
1075 (sizes 05 --- 06)
550 (sizes 07 --- 12)
700 (sizes 14 --- 17, 26)
650 (sizes 20 --- 24)
ODFLCSPD