APPENDIX C: Navigatort Display
MODE -- CONFIGURATIONS (cont)
ITEM EXPANSION RANGE UNIT DEFAULT POINT
DIS (count) DI Config Menu
GN.SW General Status Sw Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN GENS_CFG
GEN.F General Status shutdown? Yes/No Yes GENFATAL
ENT.C Enthalpy Sw Channel 0=None,
1=MBB DI12,
2=MBB DI13,
3=MBB DI14,
4=MBB DI02,
5=MBB DI04,
6=SIOB DI01
0=None ENTHCHAN
ENT.S Enthalpy Switch Type 0=NORM OPEN,
1=NORM CLSD
0=NORM OPEN ENTH_CFG
AIS Analog Input Config Menu
SRH.C SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0=None SPRHCHAN
SR.4M SPRH Sensor V alue at 4mA 0 to 100 % 0 SPRH_4MA
SR.20 SPRH Sensor Value at 20mA 0 to 100 % 1 SPRH20MA
IAQ.C IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0: no FIOP
1: FIOP
IAQ_CHAN
I.4M IAQ Sensor Value at 4mA 0 to 5000 ppm 0 IAQ_4MA
I.20M IAQ Sensor Value at 20mA 0 to 5000 ppm 2000 IAQ_20MA
OAQ.C OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0=None OAQ_CHAN
OQ.4 OAQ Sensor Value at 4mA 0 to 5000 ppm 0 OAQ_4MA
OQ.20 OAQ Sensor Value at 20mA 0 to 5000 ppm 2000 OAQ_20MA
ORH.C OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0: no Enthalpy FIOP
3: Enthalpy FIOP
OARHCHAN
OR.4 OARH Sensor Value at 4mA 0 to 100 % 0 OARH_4MA
OR.20 OARH Sensor Va l. at 20mA 0 to 100 % 100 OARH20MA
RRH.C RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0=None RARHCH AN
RR.4 RARH Sensor Value at 4mA 0 to 100 % 0 RARH_4MA
RR.20 RARH Sensor Value @ 20mA 0 to 100 % 100 RARH20MA
OC.CH OACFM Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
0=None OCFMCHAN
OC.4M OACFM Sensor Value at 4mA 0 to 100 % 0 OCFM_4MA
OC.20 OACFM Sensor Value at 20mA 0 to 100 % 100 OCFM20MA
COOL Cooling Configs Menu
N.STG Number of Cooling Stages 0to3 3 NUMCSTGS
L.CMP Low Cool Compressor 1to2 1 LC_COMP
MRT.C Compressor Min On Time 180 to 600 sec 300 C_MINON
MOT.C Compressor Min Off Time 120 to 600 sec 180 C_MINOFF
RST.C Runtime to Reset Strikes 120 to 999 sec 300 MIN_ON_S
C.INC Cool Stage Increase Time 120 to 999 sec 450 CSTAGINC
TLC Cooling SAT Trend Level --- 1 t o 1 ^F/min --- 0 . 2 SA T_TLC
SAT.U Cool Min SAT Upper Level 35.0 to 65.0 °F 53 (sizes 07--- 12)
56 (sizes 14--- 26)
SATMIN_H
SAT.L Cool Min SAT Lower Level 35.0 to 65.0 °F 42 (sizes 07--- 12)
46 (sizes 14--- 26)
SATMIN_L
RH.DB Space RH Deadband 0 % 5 SPRH_DB
HZ.OL Humidimizer Lockout Temp --- 20 to 75 °F 40 OATHLHUMZ
FOD.C Cooling Fan ---off Delay 0 to 600 sec 75 COOL_FOD
FBD.T Fan Based Dehum Type 0=NONE,
1=Comfort,
2=Max
enum 0=None FBD_TYPE
FDSM FBDH SAT Min Value 35 to 80 °F 46 FBDH_SAT
FDSP FBDH Low Set Point --- 2 0 t o 0 °Fdelta --- 2 . 5 FBDLO_ SP
FSSM FBDH S ST Min Value 10 to 60 °F 32 FBDH_SST