116
APPENDIX C: Navigatort Display
MODE -- OPERATING MODES
ITEM EXPANSION RANGE UNIT WRITE STATUS POINT
OPERATING MODES
MODE Operating Mode see Appendix B MODETEXT
SUBM O p e r a t i n g S u b --- M o d e see Appendix B SUBMTEXT
S.DMD System Demand see Appendix B SYS_DMDT
LINK Linkage Active Yes/No Yes LNK_ACT
EFF.C Cool Setpoint In Effect xx.x °F CSP_EFF
EFF.H Heat Setpoint In Effect xx.x °F HSP_EFF
T. E F F Effective Demand Temp xxx.x °F TEMP_EFF
RH.OS Occupied SPRH Setpoint 0 to 100 % SPRH_OSP
RH.US Unoccupied SPRH Setpoint 0 to 100 % SPRH_USP
CLTG Cool Mode Select T.guard xxx sec COOLMSTG
HTTG Heat Mode Select T.guard xxx sec HEATMSTG
DMD.C Space Cooling Demand xx.x °F COOL_DMD
TRD.C Cooling Demand Trend xx.x ^F/min CLDTREND
DMD.H Heating Space Demand xx.x °F HEAT_DMD
TRD.H Heat Space Demand Trend xx.x ^F/min HTDTREND
DMD.S
CDL O Cool Demand Limiting Off/On CDMLMOFF
HDLO Heat Demand Limiting Off/On HDMLMOFF
CDML Cool demand Limit Level 0to3 CDMDLLEV
HDML Heat demand Limit Level 0to3 HDMDLLEV
CL.DO Cool Demand limit offset xx.x COOLDLMO
HT.DO Heat Demand Limit offset xx.x °F HEATDLMO
MODE -- ALARMS
ITEM EXPANSION RANGE
WRITE
STATUS
POINT
ALARMS
CURR Curr Active Alarm Menu
alarm# text string ALARM01C --- ALARM25C
(repeat up to 25 times)
HIST History Menu
alarm# a l a r m # --- m m /d d / y y --- hh. m m --- t e x t st r i n g ALHIS001 --- ALHIS050
(repeat up to 50 times)
R.CUR Reset All Current Alarms Yes/No Yes ALRESET
R.HIS Alarm Reset History Menu
ARxx mm/dd/yy, hh:mm:ss ALMRES00 --- ALMRES19
(repeat up to 20 times)