APPENDIX D: SystemVut Controller CCN Tables
Status Display Tables (cont)
Tab le Display Name Range Units Point Name Write Status
GENDISP (cont)
Differential Air Quality xxxx PPM AQ_DIFF
DST currently active Yes/No DST_ACTV
Network OAT V alue xxx.x °F OAT_NET Forcible
Network Return Air Temp xxx.x °F RAT_NET Forcible
Network Space Temp Value xxx.x °F SPT_NET Forcible
Network SPRH Value 0 t o 100 % SPRH_NET Forcible
Network OARH V alue 0 to 100 % OARH_NET Forcible
Network RARH Value 0 to 100 % RARH _NET Forcible
Network IAQ V alue xxxx ppm IAQ_NET Forcible
Network OAQ V alue xxxx ppm OAQ_NET Forcible
Network OACFM Value xxx.x cfm OCFM_NET Forcible
MODEDISP
System Mode see Appendix B SYSMODE
Running Mode Operation see Appendix B SUB_MODE
Ventilation Status see Appendix B VENTSTAT
System Demand 0to99 SYS_DMD
Currently Occupied Yes/No OCCUPIED Forcible
Linkage Active Ye s/No LNK_ACT Forcible
Unocc Free Cool Active Yes/No UFC_ACT
Temp Compensate Start On Yes/No TCS_ACT
Cool Setpoint In Effect xx.x °F CSP_EFF
Heat Setpoint In Effect xx.x °F HSP_EFF
Effective Demand Temp xxx.x °F TEMP_EFF
CoolDemandLimiting Off 0to1 CDMLMOFF
Cool Demand limit offset 0to99 °F COOLDLMO
HeatDemandLimiting Off 0to1 HDMLMOFF
Heat Demand Limit offset 0to99 °F HEATDLMO
Cool demand Limit Level 0to3 CDMDLLEV
Heat demand Limit Level 0to3 HDMDLLEV
IDF_DISP
IDF Commanded RPM 0 to 100 RPM FSPD_RPM
Commanded IDF Speed 0 to 100 % FANSPEED
IDF Min RPM SP xxxx RPM RPMMINSP
IDF Minimum Fan Speed % SPEEDMIN
IDF Vent RPM SP xxxx RPM RPM_VENT
Ventilation Only IDF Spd 0 to 100 % FSPDVENT
IDF Heat RPM SP xxxx RPM RPM_HEAT
Heating IDF Speed 20 to 100 % FSPD_HT
IDF Free Cool RPM SP xxxx RPM RPM_FCL
Free Cooling IDF Speed 0 to 100 % FSPD_FCL
IDF Low Cool RPM SP xxxx RPM RPM_LCL
Low Cooling IDF Speed 20 to 100 % FSPD_LCL
IDF High Cool RPM SP xxxx RPM RPM_HCL
High Cooling IDF Speed 20 to 100 % FSPD_HCL
IDF Max RPM SP xxxx RPM RPMMAXSP
IDF Maximum Fan Speed 80 to 100 % SPEEDMAX
Fan Status Switch FAN_STAT
IDF Manual Limit Switch IDF_LSM
COOLDISP
OKtoUseFreeCooling? Yes/No OKFREECL
Free Co oling active Yes/No FREECOOL
Free Cooling SAT Setpnt xx.x °F FC_SATSP
Econo Commanded Position 0 to 100 % DAMPCMD Forcible
Commanded IDF Speed 0 to 100 % FANSPEED
Ok to use compressors? Yes/No OKMECHCL
Mechanical Cool active? Ye s/No MECHCOOL
Max Allowed Cool Stages 0to3 MAXCSTGS Forcible
Requested Cooling Stages 0to3 REQCSTGS
Actual Cool Stage Active x ACTCSTGS
Circuit A Compressor 1 On/Off COMP_A1
Circuit A Compressor 2 On/Off COMP_A2
Circuit A CMP A1 Loader On/Off COMP_ALD