138
APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables (cont)
Tab le N am e Display Name Range Units Point Name Default
ALM_CFG
ALM Relay Assigned Chan 0to2 ALM_CHAN 1=MBB RLY11
0=None
1=MBBRLY11
2=MBBRLY06
Thermostat Alerts Yes/No TSTAT_AL Yes
Hardware fa ilures Alerts Yes/No HW_AL Yes
SAT/RAT Sensor Alerts Ye s/No SATRA TAL Yes
OAT Thermistor Alerts Ye s/No OATRL_AL Yes
Space Sensors Alerts Yes/No SPACE_AL Ye s
Transducer Sensor Alerts Ye s/No TRANS_AL Yes
RH sensor failure Alert Ye s/No RHS_AL Yes
Air Quality CO2 Alerts Yes/No CO2S_AL Yes
OACFM Alarm Relay Yes/No OACFM_AL
Economizer Alerts Yes/No ECON_AL Yes
Dirty Filter Alerts Yes/No FILT_AL Ye s
General Status Alerts Yes/No GENS_AL Yes
Refrig Circuit Alerts Yes/No CKT_AL Yes
Compressor Alerts Ye s/No COMP_AL Yes
Heating failure Alerts Yes/No HEAT_AL Yes
Indoor Fan Alerts Ye s/No FAN_AL Yes
Relay on Active IOBA Yes/No IOBFA_AL
Relay on Active Faults Yes/No FAULT_AL Ye s
ZSENSCFG
Zone Sensor 1 Address 0 to 255 ZSADDR1 255
Zone Sensor 2 Address 0 to 255 ZSADDR2 255
Zone Sensor 3 address 0 to 255 ZSADDR3 255
Zone Sensor 4 address 0 to 255 ZSADDR4 255
Zone Sensor 5 address 0 to 255 ZSADDR5 255
ZS Force Unoccup enable No ZSFUNEN No
ZS Force unocc wt delay No ZSFUNWT No
Zone sensor poll rate 1 to 100 sec ZSPOLLRT 5
ZS TLO Cont Enable No ZSTLOEN No
ZS TLO set during occ No ZSTLSOC No
Zone sensor UI Mode 1=Dual Offsets ZSUIM 1=Dual Offsets
Zone sensor unit 0=degrees F ZSUNIT 0=degrees F
TOUCHCFG
System Touch Device Inst 0 to 4194303 DEVST
System Touch Poll Rate 10 to 60 sec POLLST
System Touch AI for SPT 0 to 9999 AISTSPT
System Touch AI for SPRH 0 to 9999 AISTSPRH
TRIM
OAT Sensor Trim Offset --- 10 to 10 °F OAT_TRIM 0
RAT Sensor Trim Offset --- 30 to 30 °F RAT_TRIM 0
FST Sensor Trim Offset --- 10 to 10 °F FST_TRIM 0
SPT Sensor Trim Offset --- 30 t o 30 °F SPT_TRIM 0
SPTO Sensor Offset Trim --- 1 t o 1 °F SPTOTRIM 0
SPRH Sensor Trim Offset --- 15 to 15 % SPRHTRIM
IAQ sensor trim offset --- 200 to 200 ppm IAQ_TRIM 0
OAQ Sensor Trim Offset --- 200 to 200 ppm OAQ_TRIM 0
OARH Sensor Trim Offset --- 15 t o 15 % OARHTRIM 0
RARH Sensor Trim Offset --- 15 to 15 % RARHTRIM 0
Cir.A SSP Sensor T rim --- 50 to 50 psig SSPATRIM 0
Cir.A SDP Sensor Trim --- 50 to 50 psig SDP ATRIM 0
Econ Fdback Trim Offset --- 15 t o 15 % EC1DTRIM 0
OACFM sensor trim offset --- 10 to 10 cfm OCFMTRIM 0
DISPLAY
Metric Display Yes/No DISPUNIT No
Display Language Select 0=English,
1=Spanish,
2=French,
3=Portuguese
LANGUAGE 0=English
LCD Contrast Adjustment 1to10 LCD_CONT 5
User Password Protection Enable/Disable PASS_ EBL Enable
User Password 0 to 9999 PASSWORD 1111