APPENDIX E: BACnet Points List (cont)
Point Name Typ e
BACnet
Object ID
Alias
(CCN Point Name)
BACnet Object Name
Cooling Fan --- Off Delay BMAV AV:207 cool_fod
Cooling Liquid Valve Resets Count BMAV AV:455 rs_clv_a
Cooling Liquid Valve Run H ours BMAV AV:457 hr_clv_a
Cooling Liquid Valve Starts BMAV AV:459 st_clv_a
Cooling Required BMAV AV:257 lnk_creq
Cool Set Point in Effect BMAV AV:208 csp_eff effective_cooling
Cool Shed 1 demand band BMAV AV:6014 cooling_shed1
Cool Shed 2 demand band BMAV AV:6015 coolsh1 cooling_shed2
Cool Shed 3 demand band BMAV AV:6016 coolsh2 cooling_shed3
Cool Time Select Guard BMAV AV :40 coolsh3 cl_sel_timeguard
Crankcase Heater 1 Hours BMAV AV:242 hr_cchr1 hour_cchr1
Damper Actual Position BMAV AV:2022 damppos oa_dmpr_pos
Damper Commanded Pos BMAV AV:4 dmpr_cmd
Damper Max Position BMAV AV:185 dampmax
Damper Motor Reset Count BMAV AV:102 rs_ damp
Damper Motor Run Hours BMAV AV:51 hr_damp hour_damp
Damper Motor Starts BMAV AV:139 st_damp
Damper Position BMAV AV:258 lnk_dpos
Damper Test Position BMAV AV:118 s_damper
Delay On Low SST Check BMAV AV:300 sstckdly
Demand Time Guard 1 BMAV AV:311 tdmd_tg1
Demand Time Guard 2 BMAV AV:186 tdmd_tg2
Demand Time Guard 3 BMAV AV:187 tdmd_tg3
Differential Temperature BMAV AV:78 oa_ra_diff_temp
Diffrential Enthalpy BMAV AV:77 oa_ra_diff_enth
Econo Actual Position BMAV AV:211 dampact
Economizer Travel Time BMAV AV:226 eceonotrv
Effective Deadband BMAV AV:6007 effdb effective_deadband
Effective Demand Temperature BMAV AV:163 temp_eff
EffectiveZoneSetpoint BMAV AV:6006 effsp effective_setpoint
Fan Supply Air Temp BMAV AV:10 fst idf_sa_temp
FBD Low Set Point BMAV AV:438 fbdlosp
FBD SAT Min value BMAV AV:436 fbdh_sat
FBD SST Min value BMAV AV:437 fdbh_sst
Filter Change Time BMAV AV:2019 filter_service_hrs
Filter Time Left BMAV AV:2015 filter_rntm
Free Cooling Fan Speed BMAV AV:230 fspd_free_cool
Free Cooling Reset Count BMAV AV:104 rs_free c
Free Cooling Run Hours BMAV AV:53 hr_freec hour_free_cl
Free Cooling Starts BMAV AV:141 st_freec
Full Load Reset Count BMAV AV:103 rs_fload
Heat Cool Setpoint Gap BMAV AV:238 hcsp_gap actual_min_setpoint_width
Heat Demand Trend BMAV AV:244 htdtrend
Heat DMD Offset level 1 BMAV AV:403 hdlm_level1
Heat DMD Offset level 2 BMAV AV:404 hdlm_level2
Heat DMD Offset level 3 BMAV AV:405 hdlm_level3
Heater Min Off Time BMAV AV:235 h_minoff
HeaterMinOnTime BMAV AV:236 h_minon
Heat Fan Speed BMAV AV:232 fspd_heat
Heating Demand BMAV AV:240 heat_dmd
Heating Fan--- Off Delay BMAV AV:241 heat_fod
Heating Required BMAV AV:259 lnk_hreq
Heat Level Up BMAV AV:239 hdmd_lup
Heat Select Time Guard BMAV AV:45 heatmstg ht_sel_timeguard
Heat Setpoint in Effect BMAV AV:243 hsp_eff effective_heating
Heat Shed 1 demand band BMAV AV:6011 heatsh1 heating_shed1
Heat Shed 2 demand band BMAV AV:6012 heatsh2 heating_shed2
Heat Shed 3 demand band BMAV AV:6013 heatsh3 heating_shed3
Heat Stage 1 Reset Count BMAV AV:106 rs_htr
Heat Stage 1 Run H ours BMAV AV:54 hour_htr
Heat Stage 1 Starts BMAV AV:142 st_htr
Heat Stage 1 Timeguard BMAV AV:173 timgd_h1
Heat Stage 2 Reset Count BMAV AV:107 rs_htr_2
Heat Stage 2 Run H ours BMAV AV:55 hour_htr_2