35
Table 13 — SystemVut Controller Alarm Codes (co nt)
FAULT OR ALERT
ACTION TAKEN BY
CONTROL
RESET
METHOD
PROBABLE CAUSE
A210--- GENERAL STATUS Alert Generated Automatic General Switch activation or wrong configuration
F211--- GENERAL STATUS Unit Shutdown Automatic General Switch activation or wrong configuration
F310 --- CIRA DOWN DUE TO FAIL Shutdown Circuit A Manual Compressors have 3 strikes or has been locked out by another alarm
F311--- CIRA LOW CHARGE Shutdown Circuit A Manual Low refrigerant or faulty pressure transducer
A312--- CIR.A UNEXPECTED OFF Strike for active compressors Automatic Compressor failure, transducer failure, or nuisance operating conditions
A313--- CIR.A HIGH DISCHARGE Unload compression and up
ODF to High cool speed
Automatic An overcharged system, high outdoor ambient temperature coupled with
dirty outdoor coil, plugged filter drier, or ODF speeds being set too low.
A314--- CIR.A H PS TRIP Add compressor strikes Automatic An overcharged system, high outdoor ambient temperature coupled with
dirty outdoor coil, plugged filter drier, or ODF speeds being set too low.
A315--- CIR.A LOW DISCHARGE Add compressor strikes Automatic An undercharged system, low outdoor ambient temperature coupled with
dirty outdoor coil, plugged filter drier, or ODF speeds being set too high
A316--- CIR.A LOW SUCTION Add compressor strikes Automatic Low refrigerant charge, dirty filters, evaporator fan turning backwards, loose
or broken fan belt, plugged filter drier, faulty transducer, excessively cold
return air , or stuck open economizer when the ambient temperature is low.
A317--- CIR.A PRESSURE RATIO Add compressor strikes Automatic Low refrigerant charge, plugged filter drier, faulty transducer, the ambient
temperature is low and the ODFs are running too fast.
F318--- COMPRESSOR STUCK ON Unit in Safety Shutdown Manual WeldedcontactororfrozencompressorrelayonMBB
F319--- C.A1 DOWN DUE TO FAIL Lockout Compressor A1 Manual Compressor A1 has 3 strikes or has been locked out by another alarm
A320--- C.A1 REVERSE ROTATION Add Strike for compressor A1 Automatic Wiring causing reverse rotation or faulty compressor
A321--- C.A1 FAIL TO PRESSURE Add Strike for compressor A1 Automatic Wiring causing reverse rotation or faulty compressor
F322--- C.A2 DOWN DUE TO FAIL Lockout Compressor A2 Manual Compressor A2 has 3 strikes or has been locked out by another alarm
A323--- C.A2 REVERSE ROTATION Add Strike for compressor A2 Automatic Wiring causing reverse rotation or faulty compressor
A324--- C.A2 FAIL TO PRESSURE Add Strike for compressor A2 Automatic Wiring causing reverse rotation or faulty compressor
A410--- IGC IGNITION FAILURE Lockout Heat Automatic Faulty wiring of the IGC, no gas flow, or wrong configuration
F411--- ROLLOUT WITHOUT HEAT Unit in Safety Shutdown Automatic Faulty wiring of the IGC, or rollout switch trip without a heat call
F412--- RUN AWAY HEAT Unit in Safety Shutdown Automatic Heat stuck on causing high SAT, or low air flow
A510--- INDOOR FAN STATUS Alert Generated Automatic Belt broke, moto r failure, or configuration error.
F511--- IDF OFF WHEN COMMAND ON Unit Shutdown Manual Fan stuck on, or Configuration incorrect.
F512---IDFONWHENCOMMANDOFF Unit Shutdown Manual Tripped Circuit Breaker. Broken belt. Bad indoor fan motor. Configuration
incorrect.
F600--- IDF VFD COMMUNICATION Unit Shutdown Automatic Communication failure, noise on the bus, wiring error , or configuration error.
F601--- IDF VFD UNEXPECTED Unit Shutdown Automatic VFD fault, refer to VFD section
F602--- IDF VFD LOCKOUT Unit Shutdown Power Cycle VFD locked itself out
A603--- IDF VFD IN HAND Alert Generated Automatic VFD keypad used to put the VFD in hand or off mode
F604--- IDF VFD IN HAND Unit Shutdown Automatic VFD keypad used to put the VFD in hand or off mode
A605--- IDF VFD THERMAL WARNING IDF speed reduced Automatic Motor impro per size, motor overload, or configuration errors
A606--- IDF VFD VOLTAGE WARNING IDF speed reduced Automatic Motor improper size, motor overload, or configuration errors
A607--- IDF VFD CURRENT LIMIT IDF speed reduced Automatic Motor improper size, motor overload, or configuration errors
A608--- IDF VFD WARNING IDF speed reduced Automatic Motor improper size, motor overload, or configuration errors
F611--- IDF VFD EARTH FAULT Unit Shutdown Automatic VFD fault, refer to VFD section
F612--- IDF VFD CTL WORD LOS S Unit Shutdown Automatic VFD fault, refer to VFD section
F613--- IDF VFD OVER CURRENT Unit Shutdown Automatic VFD fault, refer to VFD section
F614---IDFVFDMOTOROVERTEMP Unit Shutdown Automatic VFD fault, refer to VFD section
F615--- IDF VFD OVERLOAD Unit Shutdown Automatic VFD fault, refer to VFD section
F616--- IDF VFD UNDER VOLTAGE Unit Shutdown Automatic VFD fault, refer to VFD section
F617--- IDF VFD OVER VOLTAGE Unit Shutdown Automatic VFD fault, refer to VFD section
F618--- IDF VFD SHORT CIRCUIT Unit Shutdown Automatic VFD fault, refer to VFD section
F619--- IDF VFD MAIN PHASE LOSS Unit Shutdown Automatic VFD fault, refer to VFD section
F620--- IDF VFD PHASE U LOSS Unit Shutdown Automatic VFD fault, refer to VFD section
F621--- IDF VFD PHASE V LOSS Unit Shutdown Automatic VFD fault, refer to VFD section
F622--- IDF VFD PHASE W LOSS Unit Shutdown Automatic VFD fault, refer to VFD section
F623--- IDF VFD CONTROL VOLTAGE Unit Shutdown Automatic VFD fault, refer to VFD section
F624--- IDF VFD SUPPLY VDD Unit Shutdown Automatic VFD fault, refer to VFD section
A700--- ECON NOT MODULATING Alert Generated Automatic No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.
A701--- ECON STUCK CLOSED Alert Generated Automatic No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.
A702--- ECON STUCK OPEN Alert Generated Automatic No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.
A703--- ECON MECH DISCONNECTED Alert Generated Manual No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.
A710--- ECON NOT COOLING Alert Generated Automatic No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.
A711--- ECON IMPROPER COOLING Alert Generated Automatic No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.
A712--- EXCESSIVE OUTDOOR AIR Alert Generated Automatic No economizer motion. Check damper blades, gears, and actuator. Actuator
direction control switch (CCW, CW) wrong.