APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point
ANALOG INPUT CONFIGS (cont) Analog Inputs Configuration Menu
OAQ SENSOR CHAN OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN
OAQ PPM @ 4MA OAQ Sensor Value at 4mA 0 to 5000 ppm 0 OAQ_4MA
OAQ PPM @ 20MA OAQ Sensor Value at 20mA 0 to 5000 ppm 2000 OAQ_20MA
OARH SENSOR CHAN OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
n/a 0: no Enthalpy FIOP
3: Enthalpy FIOP
OARHCHAN
OARH RH @ 4MA OARH Sensor Value at 4mA 0 to 100 % 0 OARH_4MA
OARH RH @ 20MA OARH Sensor Va l. at 20mA 0 t o 100 % 100 OARH20MA
RARH SENS CHANNEL RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
n/a 0=None RARHCHAN
RARH RH @ 4MA RARH Sensor Value at 4mA 0 to 100 % 0 RARH_4MA
RARH RH @ 20MA RARH Sensor Va lue @ 20mA 0 to 100 % 100 RARH20MA
OACFM SENSOR CHAN OACFM Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB AI10
n/a 0=None OCFMCHAN
OACFM @ 4MA OACFM value at 4mA 0 to 100 CFM 0 OCFM_4MA
OACFM @ 20MA OACFM Value @ 20mA 0 to 100 CFM 20 OCFM20MA
COOLING Cooling Configurations Menu
COOLING STAGE QTY Number of Cooling Stages 0to3 3 NUMCSTGS
LOW COOL COMP Low Cool Compressor 1to2 1 LC_COMP
COMP MIN ON TIME Compressor Min On Time 180 to 600 sec 300 C_MINON
COMP MIN OFF TIME Compressor Min Off Time 120 to 600 sec 180 C_MINOFF
STRIKE CLEAR TIME Runtime t o Reset Strikes 120 to 999 sec 300 MIN_ON_S
COOL STAGEUP TIME Cool Stage Increase Time 120 to 999 sec 450 CSTAGINC
COOL SATTREND LEV Cooling SAT Trend Level --- 1 . 0 t o 1 . 0 ^F/min --- 0 . 2 SA T_TLC
UPPER MIN SAT Cool Min SAT Upper Level 35.0 to 65.0 °F 56 (sizes 04--- 06)
53 (sizes 07--- 12)
56 (sizes 14--- 26)
SATMIN_H
LOWER MIN SAT Cool Min SAT Lower Level 35.0 to 65.0 °F 46 (sizes 04--- 06)
42 (sizes 07--- 12)
46 (sizes 14--- 26)
SATMIN_L
SPRH DEADBAND Space RH Deadband 0 % 5 SPRH_D8
HUMZ LOCKOUT OAT Humidimizer Lockout Temp --- 20 to 75 °F 40 OATLHUMZ
COOL FANOFF DELAY Cooling Fan --- off Delay 0 to 600 sec 75 COOL_FOD
FBD TYPE FBD CONTROL TYPE 0=None,
1=Comfort,
2=Max
0=None FBD_TYPE
FBD SAT MIN VALUE FBD SAT MIN VALUE 35 to 80 °F 46 FBDH_ SAT
FBD LOW SP FBD LOW SP --- 2 0 t o 0 °Fdelta --- 2 . 5 FBDLO_SP
FBD SST MIN VALUE FBD SST MIN VALUE 10 to 60 °F 32 FBDH_SST
LOW AMBIENT LOW AMBIENT CONFIGS MENU
CIR.A LOCKOUT OAT CircuitALockoutTemp --- 20 to 75 °F 0: no Economizer FIOP
40: Economizer FIOP
OATLCMPA
LOW AMBIENT TEMP Low Ambient Temperature 0to80 °F 66 LA_TEMP
LOW COOL MIN OAT Low Cool lockout Temp --- 20 to 60 °F 10 (sizes 04--- 06)
30 (sizes 07--- 12)
40 (sizes 14--- 26)
LCLOCKSP
MED COOL MIN OAT Medium Cool lockout Temp --- 20 t o 60 °F 20 (sizes 07--- 12)
30 (sizes 14--- 26)
MCLOCKSP
LA DEHUM LEV 1 Low Ambient Dehum Lev 1 40 to 125 °F 80 LAHTEMP1
LA DEHUM LEV 2 Low Ambient Dehum Lev 2 40 to 125 °F 61 LAHTEMP2
LA DEHUM LEV 3 Low Ambient Dehum Lev 3 40 to 125 °F 55 LAHTEMP3
LA DEHUM SDT SP 1 LA Dehum SDT SP Lev 1 60 to 120 °F 82 LHSDTSP1
LA DEHUM SDT SP 2 LA Dehum SDT SP Lev 2 60 to 120 °F 93 LHSDTSP2
LA DEHUM SDT SP 3 LA Dehum SDT SP Lev 3 60 to 120 °F 104 LHSDTSP3
HUMZ ENABLE Humidimizer Status Ye s/No enum No for all except
Humidimizer units
HUMZ_EN
RDVA ENABLE Reheat Dischg Valve CirA Yes/No enum No for all except
Humidimizer units
RDVA_EN
RLVA ENABLE Reheat Liquid Valve CirA Ye s/No enum No for all except
Humidimizer units sizes
04--- 06
RLVA_EN
CLVA ENABLE Cooling Liq Valve CirA Yes/No enum No for all except
Humidimizer units sizes
04--- 06
CLVA_EN