APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point
ODF SETTINGS (cont) Outdoor Fans Configurations Menu
ODF MBIAS 3 ODF Map Bias Term 3 --- 200 to 200.00 20.93 (sizes 04--- 06)
0 (sizes 07, 14--- 20)
65.29 (sizes 08--- 12)
114.74 (sizes 24--- 26)
ODFBIAS3
ODF SWITCH POINT1 ODF Fan Switch Point 1 --- 100 to 100.00 3.68 (size 07)
3.4 (sizes 08--- 12)
4.84 (sizes 14--- 20)
1.58 (sizes 24--- 26)
ODFPIUP1
ODF SWITCH POINT2 ODF Fan Switch Point 2 --- 100 to 100.00 17.1 (size 07)
9.06 (sizes 08--- 12)
22.3 (sizes 14--- 20)
10.44 (sizes 24--- 26)
ODFPIUP2
ODF SWITCH POINT3 ODF Fans Switch Point 3 --- 100 t o 100.00 100 (sizes 07, 14--- 20)
19.76 (sizes 08--- 12)
20.93 (sizes 24--- 26)
ODFPIUP3
ODF PROP PR ODF Proportional ctrl Pr --- 100 t o 100.00 1.4 (sizes 04--- 06)
25 (sizes 07--- 12)
50 (sizes 14--- 26)
ODFPR_KC
ODF MSLOPE 1 ODF Map Slope Term 1 --- 100 t o 100.00 55.3 (sizes 04--- 06)
25.3 (size 07)
60.09 (sizes 08--- 12)
31 (sizes 14--- 20)
55.33 (sizes 24--- 26)
ODFSLPE1
ODF MSLOPE 2 ODF Map Slope Term 2 --- 100 t o 100.00 19.07 (sizes 04--- 06)
9 (size 07)
18.69 (sizes 08--- 12)
9.6 (sizes 14--- 20)
19.07 (sizes 24--- 26)
ODFSLPE2
ODF MSLOPE 3 ODF Map Slope Term 3 --- 100 t o 100.00 8.85 (sizes 04--- 06)
1 (sizes 07, 14--- 20)
9.34 (sizes 08--- 12)
8.85 (sizes 24--- 26)
ODFSLPE3
HEATING Heating Configurations Menu
UNIT TYPE OF HEAT Type of Heat Installed 0=ELECTRIC,1=GAS 0(50series)
1(48series)
HEATTYPE
HEATING STAGE QTY Number of Heating Stages 0to2 2 (all except below);
0(50serieswithout
FIOP heat),
1 (50 Series, si zes 04--- 06
low or medium heat),
1 (50 series, sizes
07--- 14 and low heat),
1 (50 series, siz es 07---12
and mediu m heat)
NUMHSTGS
HEAT MIN ON Heat Minimum On Time 60 to 600 sec 120 H_MINON
HEAT MIN OFF Heat Minimum Off Time 60 to 600 sec 120 H_MINOFF
HEAT STAGEUP TIME Heat Stage Increase Time 120 to 999 sec 450 HSTAGINC
HEAT SATTREND LEV Heating SAT Trend Level --- 1 t o 1 . 0 ^F/min 0.2 SAT_TLH
LOWER MAX SAT Heat Max SAT Lower Level 85.0 to 200.0 °F 140 SATMAX_L
UPPER MAX SAT Heat Max SAT Upper Level 85.0 to 200.0 °F 160 SATMAX_H
HEAT FANOFF DELAY Heating Fan--- off Delay 10 to 600 sec 30 (50 series)
45 (48 series)
HEAT_FOD
HEAT LOCKOUT OAT Heating Lockout Temp 40 to 125 °F 75 OATLHEAT
SAT DURING HEAT? SAT Heat Mode Sensing Enable/Disable Disable SAT_HEAT
IGC IFO TIMEOUT No IGC IFO input Timeout 0to60 min 5 NO_IGCTM
PREHEAT W/O IDF? Pre --- Heat HX without IDF? Enable/Disable Disable PREHT_HX
PREHEAT F AN DELA Y Pre---HeatFanOnDelay 0 to 120 sec 30 PREHT_TM
SA TEMPER ENABLED SupplyAirTemperingEnable Yes/No Yes SATEMPEN
SA TEMPER SET PNT SA tempering Set point xx °F 50 SATEMPSP
TEMPER MAX OUT Max OAT for SA tempering --- 40 to 125 °F 48 OATSTEMP
INDOOR FAN Indoor Fan Configurations Menu
OCCUPIED FAN? FanOnWhenOccupied Ye s/No Yes FANON_OC
INDOOR FAN TYPE Indoor Fan Type 0=None
1=VFD
2=Direct Drive
1 1=Allunitsexceptsizes
04---06 fan option “0”
2=fanoption0onsizes
04--- 06
IDFTYPE
DIR DRV IDF SPDS Direct Drive Fan Speeds 2=2
3=3
2 2=fanoption0onsizes
04--- 06
NUMFSPDS
SHUTDOWN IDF FAIL Shut Down on IDF Failure Ye s/No enum No FATALFAN
IDF VFD VOLTAGE IDF VFD Nom. Motor Volts 50 to 100 volts See VFD Motor Default
Configuration Tables.
For sizes 04--- 06 see
Ta b le 3 2 .
For size 07--- 26 V ertical
units see T able 39.
Fo r s i z e 0 7 --- 2 6 H o ri z o n t a l
units see T able 40.
MOTVOLT