APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
Display Text Expanded Text Range Units Default Point
ECONOMIZER (cont) Economizer Configurations Menu
MDD--- MIN MOVE T24Econ Min Move for SAT 10 to 20 % 10 T24ECSTS
M D D --- S A T D B Damper SAT deadband 0 to 20.0 °F 12 T24SATDB
M D D --- M I N R A T --- O A T T24 Min Diff in RAT--- OAT 5.0 to 20.0 °F 15 T24RATDF
MDD--- MIN TEST POS T24 Test Minimum Pos 0 to 100 % 15 T24TSTMN
MDD--- MAX TEST POS T24 Test Maximum Pos 0 to 100 % 85 T24TSTMX
AIR QUALITY Air Quality Configurations Menu
ANALOG IAQ CTRL Analog Input IAQ Control 0=NO IAQ,
1=DCV,
2=IAQ OVRD,
3=CTRL MINP
0: no FIOP
1: FIOP
IAQANCFG
IAQ POS @ MAX SPD IAQ Position at Max Fan 0 to 100 % 10 IAQMINP
LOW AIR.Q DIFF AQ Differential Low 0 to 5000 ppm 100 DAQ_LOW
HIGH AIR.Q DIFF AQ Differential High 0 t o 5000 ppm 700 DAQ_HIGH
PREOCC PURGE ENBL IAQ Preoccupancy Purge Ye s/No Yes IAQPURGE
PURGE POS @ MAX IAQ Purge Pos at Max IDF 0 to 100 % 40 IAQPMAX
PREOCC LOW LIMIT Preocc Purge Lockout OAT 0to70 °F 50 IAQP_LA
PREOCC PURGE TIME Preocc Purge Duration 5 to 120 min 15 IAQPTIME
A Q D I F H I --- I A Q O V R AQ Diff High IAQOVERRIDE 0 to 5000 PPM 700 AQD_HIGH
A Q D I F LO --- I A Q O V R AQ Diff Low--- IAQ OVERRIDE 0 to 5000 PPM 100 AQD_LOW
IAQ OVRRD ENABLE IAQ override enable Ye s/No enum No IAQOVREN
ALARM RELAY Alarm Relay Configurations Menu
ALM RELAY CHANNEL ALM Relay Assigned Chan 0=NONE,
1=MBB RLY11,
2=MBB RLY06
1=MBB RLY11 ALM_CHAN
THERMOSTAT ALERTS Thermostat Alerts Yes/No Yes TSTAT_AL
HARDWARE ALERTS Hardware failures Alerts Yes/No Yes HW_AL
SAT/RAT ALERTS SAT/RAT Sensor Alerts Ye s/No Yes SATRA TAL
OAT SENSOR ALERTS OAT Thermistor Alerts Ye s/No Yes OATRL_AL
SPACE SENS ALERTS Space Sensors Alerts Ye s/No Yes SPACE_AL
TRANSDUCER ALERTS Transducer Sensor Alerts Yes/No Yes TRANS_AL
RH SENSOR ALERTS RH sensor failure Alert Yes/No Yes RHS_AL
CO2 SENSOR ALERTS Air Quality CO2 Alerts Yes/No Yes CO2S_AL
OACFM SENS ALERTS OACFM Alarm Relay Yes/No Yes OACFM_AL
ECONOMIZER ALERTS Economizer Alerts Yes/No Yes ECON_AL
AIRFILTERALERTS Dirty Filter Alerts Yes/No Yes FILT_AL
GEN STATUS ALERTS General Status Alerts Yes/No Yes GENS_AL
REFRIG CIR ALERTS Refrig Circuit Alerts Yes/No Yes CKT_AL
COMPRESSOR ALERTS Compressor Alerts Yes/No Yes COMP_AL
HEATING ALERTS Heating failure Alerts Ye s/No Yes HEAT_AL
INDOOR FAN ALERTS Indoor Fan Alerts Ye s/No Yes FAN_AL
VFD ALERTS VFD Alerts Yes/No Yes VFD_AL
IO BOARD ALERTS Relay On Active IOBA Yes/No No IOBFA_AL
ON ACTIVE FAULTS Relay on Active Faults Yes/No Yes FAULT_AL
NEW HARDWARE Quick Menu for New Hardware
UNIT CONTROL TYPE Unit Control Type 0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=TSTAT CTRLTYPE
ECON INSTALLED? Economizer Installed? Yes/No No: no FIOP
Yes: FIOP
ECONO
SPRH SENS CHANNEL SPRH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08,
4=SIOB Ai10
0=None SPRHCHAN
IAQ SENSOR CHAN IAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
1: no FIOP
0: FIOP
IAQ_CHAN
OAQ SENSOR CHAN OAQ Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None OAQ_CHAN
OARH SENSOR CHAN OARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
3: no FIOP
0: FIOP
OARHCHAN
RARH SENS CHANNEL RARH Assigned Channel 0=None,
1=MBB AI06,
2=MBB AI07,
3=MBB AI08
0=None RARHCHAN