APPENDIX A: SystemVut Controller Display
Outputs Main Menu Layou t
Display Text Expanded Text Values Units Write Status Point
OUTPUTS Outputs Menu
GENERAL OUTPUTS General Outputs Menu
IDF SPEED OUTPUT Commanded IDF Speed 0 to 100 % F ANS PEED
ECON CMD POSITION Econo Commanded Position 0 to 100 % Forcible DAMPCMD
RHT DISCH VALVE A Reheat Dischg Valve CirA Enable/Disable RDV_A
COOLING LV A Cooling Liq Valve CirA Enable/Disable CLV_A
CCH RELAY CCH Relay 1 State On/Off CCHR1
PE1 RELAY Power Exhaust 1 Relay On/Off Forcible PE1
PE2 RELAY Power Exhaust 2 Relay On/Off Forcible PE2
ALARM RELAY Alarm Output Relay State On/Off Forcible ALMOUT
DD IDF HI SPD RLY DD IDF high speed relay On/Off FSPDHRLY
DD IDF MD SPD RLY DD IDF med. Speed relay On/Off FSPDMRLY
DD IDF LO SPD RLY DD IDF low speed relay On/Off FSPDLRLY
COOLING OUTPUTS Cooling Outputs Menu
COMPRESSOR A1 Circuit A Compressor 1 On/Off COMP_A1
COMPRESSOR A2 Circuit A Compressor 2 On/Off COMP_A2
COMMANDED ODF SPD Commanded ODF Speed xxxx rpm ODFSPD
ODF SPEED OUT 1 ODF Speed Signal Output1 xxxx rpm ODF1SPD
ODF SPEED OUT 2 ODF Speed Signal Output2 xxxx rpm ODF2SPD
ODF SPEED OUT 3 ODF Speed Signal Output3 xxxx rpm ODF3SPD
HEATING OUTPUTS Heating Outputs Menu
HEAT 1 RELAY Heat Stage 1 Relay On/Off HEAT_1
HEAT 2 RELAY Heat Stage 2 Relay On/Off HEAT_2
USB Main Menu Layout
Display Text Expanded Text Values Units Write Status Point
USB USB Menu
DATA ACQUISITION Data Acquisition Menu
TREND ST ATUS USB TREND STATUS 0=IDLE,
1=TRENDING,
2=NO POINTS,
3=USB FULL
TRNDSTAT
TREND DURATION USB TREND DURATION 0=1 MINUTE,
1=5 MINUTES,
2=15 MINUTES,
3=30 MINUTES,
4=1 HOUR,
5=3 HOURS,
6=8 HOURS,
7=12 HOURS,
8=1 DAYS,
9=1.5 DAYS,
10=2 DAYS,
11=3 DAYS,
12=5 DAYS,
13=1 WEEK,
14=2 WEEK,
15=4 WEEK,
16=USB FULL
Command TRNDDUR
TREND RATE USB TREND RATE 1 t o 300 Command TRNDRATE
TREND POINTS FROM USB TREND POINTS FROM 0=FILE,
1=LIST
Command TRNDPNTS
TREND FROM USB FILE? TREND FROM USB FILE MENU
TREND FROM PRELIST? TREND FROM PRELIST MENU
EQUIP PERFORMANCE TREND EQUIP PERFORMANCE On/Off Command TRNDEQPR
GEN. INPUT/OUTPUT TREND GEN INPUTS/OUTPUTS On/Off Command TRNDIO
COOL PERFORMANCE TREND COOL PERFORMANCE On/Off Command TRNDCLPR
HEAT PERFORMANCE TREND HEAT PERFORMANCE On/Off Command TRNDHTPR
COOL DIAGNOSTIC TREND COOLING DIAGNOSTIC On/Off Command TRNDCLDG
IDF DIAGNOSTIC TREND IDF DIAGNOSTIC On/Off Command TRNDIDF
VENT DIAGNOSTIC TREND VENTILATION On/Off Command TRNDVENT
TREND GO? Start USB Trending Yes/No Command TREND_EN
SAVE CONFIGS TO FILE Save Configuration to file
SAVE CONFIGS Make Config Backup File Start/Stop Command DDBCKUP
SAVE CONFIG STATUS Backup File is ready 0=IDLE,
1=SUCCESS,
2=FAILURE
BACKUP_R
SAVE CONFIGS FROM FILE Save Configuration from file
FIND CONFIG FILE USB Find Restore File Yes/No Command BACKFILE
FILE TRANSFER File Transfer Menu
BACKUP SERVICE FILES BACKUP SERVICE FILES
UPGRADE SOFTWARE Upgrade Software Menu
FIND APPLICATION FILE USB search for app file Yes/No Command APPFILE