3
LEGEND
NOTES FOR FIG. 1, 7
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
3. Set heat anticipator at .14 amp for units with 2 stages of heating.
Set stage two anticipator at .14 amps.
4. Use copper conductors only.
5. TRAN is wired for 230-v unit. If unit is to be run with 208-v power
supply, disconnect BLK wire from 230-v tap and connect to 208-v
tap (RED). Insulate end of 230-v tap (ORN).
NOTES FOR FIG. 2, 5, 8, 10, 12, 15
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at .14 amp for units with 2 stages of heating.
Set stage two anticipator at .14 amps.
5. Use copper conductors only.
6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power
supply, disconnect BLK wire from 230-v tap (ORN) and connect
to 208-v (RED). Insulate end of 230-v tap.
NOTES FOR FIG. 3, 4, 6, 9, 11, 13, 14, 16, 17
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at .14 amp for units with 2 stages of heating.
Set stage two anticipator at .14 amps.
5. Use copper conductors only.
AHA
Adjustable Heat Anticipator
C—
Contactor, Compressor
CAP.
Capacitor
CB
Circuit Breaker
CC
Cooling Compensator
COMP
Compressor Motor
D—
Diode
DAT
Discharge Air Thermistor
DX
Direct Expansion
EC
Enthalpy Control
ECON
Economizer
EPS
Emergency Power Supply
(Nine-Volt Battery)
EQUIP
Equipment
ER
Economizer Relay
FPT
Freeze-Up Protection Thermostat
GND
Ground
HPS
High-Pressure Switch
HS
Hall Effect Sensor
I—
Ignitor
IAQ
Indoor Air Quality
IDM
Induced-Draft Motor
IFC
Indoor-Fan Contactor
IFM
Indoor-Fan Motor
IFMOVL
Indoor-Fan Motor Overload
IGC
Integrated Gas Unit Controller
LED
Light-Emitting Diode
LPS
Low-Pressure Switch
LS
Limit Switch
MGV
Main Gas Valve
MTR
Motor
OAT
Outdoor-Air Thermostat
OFC
Outdoor-Fan Contactor
OFM
Outdoor-Fan Motor
OLR
Overload Relay
P—
Plug
PL
Plug Assembly
QT
Quadruple Terminal
R—
Relay
RS
Rollout Switch
SAT
Supply-Air Thermostat
SEN
Sensor
ST
Start Thermistor
SW1
Switch Fully Open
SW2
Switch Fully Closed
SW3
Switch Minimum Vent Position
SW4
Switch Maximum Vent Position
TC
Thermostat, Cooling
TDR
Time-Delay Relay
TH
Thermostat, Heating
TRAN
Transformer
VVT
Variable Volume/Variable Temperature
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only.
Not to represent wiring.
Ground
|(
Capacitor