UNIT
STD. UNIT
WEIGHT
ECONOMIZER WEIGHT
CORNER
WEIGHT
(A)
CORNER
WEIGHT
(B)
CORNER
WEIGHT
(C)
CORNER
WEIGHT
(D)
Varislide™ PARABLADE
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
48TJF/TJE004 460 209 34 15.4 42 19.1 140 63.5 105 47.6 159 72.1 56 25.4
48TJD/TJE/TJF005 470 213 34 15.4 42 19.1 142 64.4 106 48.1 162 73.5 60 27.2
48TJD/TJE/TJF006 490 222 34 15.4 42 19.1 150 68.0 115 52.2 160 72.6 65 29.5
48TJD/TJE/TJF007 565 256 34 15.4 42 19.1 165 74.8 136 61.7 200 90.7 64 29.0
LEGEND
LED Light-Emitting Diode
*Indicates horizontal center of gravity.
†Indicates vertical center of gravity.
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity.
3. Direction of airflow.
4. On vertical discharge units, ductwork should be attached to accessory roof
curb only. For horizontal discharge units, field-supplied flanges should be
attached to horizontal openings.All ductwork should be attachedto the flanges.
5. Minimum clearances (local codes or jurisdiction may prevail):
a. Between unit, flue side, and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb) 1 inch. Bot-
tom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The
side getting the greater clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC (National Electrical Code).
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces,
control box side, 42 in. per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion
side as stated in notes 5a, b, and c, a removable fence or barricade requires
no clearance.
7. Units may be installed on combustible floors made from wood or class A, B,
or C roof covering material if set on baserail.
CONNECTION SIZES
A 1
1
16
9 Dia. (27) Field Power Supply Hole
B
3
4
9−14 NPT Condensate Drain
C
1
2
9−14 NPT Gas Connection
Fig. 6 Base Unit Dimensions