10
ELECTRIC HEATER DATA
LEGEND
*May be field converted to single-phase units, see electric heat installation instructions.
NOTE: Separate power source is required for all heaters. Control from base unit 50AH (24 v).
ELECTRIC HEATER
UNIT 88EN
USED WITH
UNIT 50AH
V-PH
(60 Hz)
CAP. (kW)
BRANCH CIRCUIT
Heater Amps MCA MOCP (Amps)
0050CA01
024, 036
1-Stage Heat
240-1 5.0 20.8 26.0 30
0075CA01 240-1 7.5 31.3 39.1 40
0115CA01 240-1 11.5 47.9 59.9 60
0075EA01
208-3 5.6 15.6 19.5 20
240-3 7.6 18.0 22.6 25
1150EA01
208-3 11.3 31.2 39.0 40
240-3 15.0 36.1 45.1 50
0100EA01
048, 060
2-Stage Heat
208-3 7.5 20.8 26.0 30
240-1* 10.0 41.7 52.1 60
240-3 10.0 24.1 30.1 35
0150EA01
208-3 11.3 31.2 39.0 40
240-1* 15.0 62.5 78.1 80
240-3 15.0 36.1 45.1 50
0200EA01
208-3 15.0 41.7 52.1 60
240-1* 20.0 83.3 104.2 110
240-3 20.0 46.9 58.6 60
0300EA01
208-3 22.5 62.5 78.2 80
240-3 30.0 72.2 90.2 100
0300CA01 240-1 30.0 124.0 155.0 175
0100FA01 480-3 10.0 12.0 15.0 15
0150FA01 480-3 15.0 18.1 22.6 25
0200FA01 480-3 20.0 24.1 30.1 35
0300FA01 480-3 30.0 36.1 45.1 50
MCA Minimum Circuit Ampacity
MOCP Maximum Overcurrent Circuit Protection
(Fuses or Circuit Breaker)
Electrical data (cont)