EasyManua.ls Logo

Carrier 50GJ006 - Page 11

Carrier 50GJ006
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 2B Electrical Data (Units With Electrical Convenience Outlet)
UNIT
50GJ
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
(each)
IFM
ELECTRIC
HEAT*
POWER SUPPLY
MINIMUM UNIT
DISCONNECT SIZE
Min Max RLA LRA FLA FLA Nominal kW† FLA MCA MOCP FLA LRA
006
(5 Tons)
208/230-3-60 187 254 17.3 123.0 1.5 5.8
4.9/ 6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
34.9/34.9
34.9/34.9
39.6/43.8
53.9/60.4
67.0/75.4
81.3/91.9
40/ 40**
40/ 40**
45/ 50**
60/ 70
70/ 80
90/100
34/34
34/34
37/41
51/56
63/70
76/86
173/173
460-3-60 414 508 9.0 62.0 0.8 2.6
6.0
11.5
14.0
23.0
25.0
7.2
13.8
16.8
27.7
30.1
17.4
17.4
23.3
27.0
40.6
43.6
20**
20**
25**
30**
45**
45**
17
17
21
25
37
40
87
575-3-60 518 632 7.1 50.0 0.8 2.6 13.8 20** 13 61
008
(7
1
2
Tons)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
7.8/10.4
12.0/16.0
18.6/24.0
24.0/32.0
31.9/42.4
21.7/ 25.0
33.3/ 38.5
51.6/ 57.7
66.7/ 77.0
88.5/102.0
44.2/ 44.2
44.2/ 45.6
56.0/ 62.5
78.9/ 86.5
97.8/110.6
125.1/141.9
50/ 50**
50/ 50**
60/ 70
80/ 90
100/125
150/150
46/ 46
46/ 46
52/ 58
74/ 81
91/103
116/131
247/247
460-3-60 414 508 6.4 44.0 0.7 3.4
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
21.9
27.8
31.8
48.7
56.6
69.6
25**
30**
35**
50**
60**
70
23
26
29
45
52
64
124
575-3-60 518 632 4.8 34.0 0.7 3.4
17.0
34.0
17.1
34.1
16.8
27.4
48.8
20**
30**
50**
17.5
25.2
44.8
97
012
(10 Tons)
208/230-3-60 187 254 17.3 123.0 1.4 10.6
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.6/50.0
21.7/ 25.0
33.3/ 38.5
66.6/ 77.0
88.4/102.0
104.4/120.3
58.3/ 58.3
58.3/ 58.3
59.9/ 66.4
101.5/114.5
128.7/145.8
148.7/138.5
70/ 70
70/ 70
70/ 70
110/125
150/150
150/175
61/ 61
61/ 61
61/ 62
94/106
119/135
137/156
341/341
460-3-60 414 508 10.0 62.0 0.7 4.8
16.5
27.8
33.0
41.7
50.0
19.8
33.4
39.7
50.2
60.1
31.4
33.6
50.5
58.4
71.4
68.9
35**
35**
60**
60**
80
90
33
33
46
54
66
77
172
575-3-60 518 632 7.9 50.0 0.7 4.8
17.0
34.0
51.0
17.1
34.1
51.2
24.9
28.9
50.2
58.8
30**
30**
60**
70
26
26
46
66
138
LEGEND FOR TABLES 2A AND 2B
CUL Canadian Underwriters’ Laboratories
FLA Full Load Amps
HACR Heating, Air Conditioning
and Refrigeration
IFM Indoor (Evaporator)
Fan Motor
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent
Protection
NEC National Electrical Code
OFM Outdoor (Condenser) Fan Motor
RLA Rated Load Amps
*Heaters are field installed only.
†Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v, or 575 v. If power distribution voltage to unit varies from rated
heater voltage, heater kW will vary accordingly.
**Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
nation load and equipment (refer to NEC Articles 430 and 440),
the overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%.
Use the following formula to determine
the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
EXAMPLE: Supply voltage is 460-3-60
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
1371
=
3
= 457
Determine maximum deviation from average voltage:
(AB) 457 452=5v
(BC) 464 457=7v
(AC) 457 455=2v
Maximum deviation is 7 v.
Determine percentage of voltage imbalance:
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2% contact your local electric utility company
immediately.
3. 575-v units have CUL approval only.
11

Related product manuals